CAUTIONS
• Use this device with
copper or copper clad wire only.
• For indoor applications only.
•
SAVE THESE INSTRUCTIONS.
Black
Blue
Black
Hot (Black)
Gray
Neutral (White)
Line,
120/277VAC,
50/60Hz
Electrical Box
White
White
Sleeve
Violet
Connectors
Green
Ground
Load
0-10V
control
RF Wireless Load Control 20A Switching Relay,
RF Wireless Load Control 0-10V Dimmer
and RF Wireless Load Control 800W Dimmer
Cat. Nos. LU20S, LU107 and LU04P
INSTALLATION INSTRUCTIONS
ENGLISH
PK-A3314-10-00-2A
Before Installation
• Install to outside or inside of junction box or outside of luminaire.
• If mounted inside, a plastic cover must be used (metal will limit the RF signal).
• LU107 uses 0-10Vdc low voltage control wires which may be installed as Class 1
or Class 2.
NOTE
(LU107): 0-10V Control Wiring - Connect the violet wire to the + 0-10V line
and the gray wire to the 0-10V common using Class 1 or Class 2 wiring methods
DVLQGLFDWHGLQWKHVHLQVWUXFWLRQVEDOODVW¿[WXUHGULYHULQVWUXFWLRQVRUEDOODVW¿[WXUH
driver label markings. Observe all requirements of any authority having jurisdiction
with respect to wire type, sleeving, isolation methods, and the like.
WARNINGS
•
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes
and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
PK-A3314-10-00-2A
© 2020 Leviton Mfg. Co., Inc.
2
.
6WULSZLUHVLQDQGFRQQHFWDVSHUZLULQJGLDJUDP(QVXUHZLUHVDUH¿UPO\
attached and there is no exposed copper.
a. LU107 Wiring Diagram
Product Description
Lumina RF Load Controllers are a component within a larger wireless control system.
They require a compatible Room Controller for enrollment and creation of networks
and ultimately to determine system functionality.
Lumina RF Devices communicate with each other, and the Room controller, via a
2.4Ghz radio on a wireless mesh network. Each line voltage powered device is a
repeater to ensure the signal get's out to all parts of the network.
c. LU04P Wiring Diagram
Black
Load
Hot (Black)
Black
Neutral (White)
Blue
White
White
Green
Ground
Line
120 VAC,
60Hz
4.
&RQ¿UPV\VWHPZLULQJE\XVLQJWKHWHVWEXWWRQWRWXUQRQRIIWKHGHYLFHDQGF\FOH
WKURXJKSUHVHWGLPPLQJOHYHOV7KLVZLOOFRQ¿UPWKDWZLULQJLVFRPSOHWH
5.
3URFHHGWRV\VWHPFRQ¿JXUDWLRQDQGSURJUDPPLQJ5HIHUWR\RXUURRP
controller.
WARNING
:
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER
at circuit
breaker or fuse and test that power is off before wiring!
1
.
Mount the Load Control device to junction box or luminaire through
1/2 in hole or knockout and secure with provided locknut.
ATTENTION
: For LU04P, ensure the thermal pad is in contact with the metal
junction box. LU04P is not to be installed in enclosed junction box.
Installation
b. LU20S Wiring Diagram
Line
120/277VAC,
50/60Hz.
Blue
White
Hot (Black)
Black
Neutral (White)
White
Load
Green Ground
3.
Restore power at circuit breaker or fuse.
LU04P
thermal pad
®
6\VWHP&RQ¿JXUDWLRQDQG3URJUDPPLQJ
1.
Devices must be enrolled to a room controller for system functionality.
Enrollment method/process varies by device type.
a.
LU107, LU20S
Devices are in “auto-join” mode when they power up. This means they are
seeking a network and will join a Room Controller when it allows them to join
with no specific action required by the user. Refer to your Room Controller
programming information for more details
If your LU107/LU20S does not join automatically, reset it to factory factory
defaults and try again
b.
LU04P
i.
Device enrollment must be triggered manually
ii. Put your Room Controller in enrollment mode.
iii.
Press and Hold the Toggle/Reset button for 7 seconds, then release. The
LED will blink amber. Press and release the button without holding. The
LED will flash green and it will start seeking a network
iv. When enrollment has been completed:
1. Successful enrollment: The locator LED will blink GREEN 3 times.
2. Failed enrollment: The locator LED will blink RED 3 times.