Leviton JCC Emergency Series Installation Instructions Download Page 1

Installation instructions for JC110002 Emergency Downlight

Emergency Range

company

a

 

Important warranty information

This product is supported by a 2-year standard warranty which will extend to 5 years if registered within the first year of purchase.

(5 year on batteries). Please register at jcc.co.uk/warranty - Terms and conditions apply.

The installer will be asked to provide the following information, which is detailed on a label attached to the luminaire’s chassis: 

Product Code/Date Code.

JCC Lighting Products Ltd. Innovation Centre, Beeding Close, Southern Cross Trading Estate, Bognor Regis, West Sussex, PO22 9TS, United Kingdom

Technical Support: +44(0)1243 838986   Customer Services: +44(0)1243 838999

BS EN ISO9001 - 2015 - Registered Firm Certificate No. GB 1552

V5_August_2021_RS

Warnings & Cautions

• 

To avoid electric shock, serious injury or property damage,  
isolate power before installing, removing or servicing the product.

• 

It is recommended that luminaires are installed by a qualified 

 

electrician to ensure the installation complies with the local current 
wiring regulations. 

• 

It may be necessary to upgrade your MCBs to allow for increased 
inrush current. 

• 

This product is designed for connection to a 220-240V~ 50/60Hz.

• 

It is recommended that the ambient room temperature should not 

exceed 26°C.

• 

All testing should be carried out in accordance to 

EN 50172:2004

• 

The light source of this luminaire is not replaceable: when the light source 
reaches the end of its life the whole of the luminaire must be replaced.

• 

Read instructions and check that you have all of the tools and  
accessories required to complete the installation correctly.  
Isolate power supply before starting installation. 

• 

Do not carry out insulation tests with the product connected to  

the circuit.

• 

Any broken or damaged parts should be replaced as soon as possible. 
JCC will not accept responsibility for claims arising from sub-standard 
installations; which will void the warranty.

• 

This luminaire is for indoor only

INSTALLATION

ENGLISH

RoHS

Compliant

IP20

jcc

.co.uk

Colour temp: 6000K    Ra: 72

3.5W 220-240V~ 50/60Hz - Class II

Cut out Ø

Profile & Dimensions

All dimensions in millimetres

Non-replaceable control gear  Non-replaceable light source

LED

LED

Light source:

 Wattage:

Lumens:

Integral LED

3.5W

110 lumens

 Non-Maintained

(3NM)

 + Light off 24/7

 + Emergency

1.  Cut the mounting hole in the ceiling. (JCC recommends that a sample 

hole is cut in a section of spare material to familiarize yourself with the 
process). 

2.  Connect luminaire to 220-240V~ supply as shown above.
3.  Batteries are already connect and do not require any further action 

prior to commisioning

4.  Feed the inverter and battery pack through the opening, then press the 

springs back and push luminaire body into aperture

5.  Switch on mains supply and test for operation 

(allow 24hrs for batteries to charge).

6. 

Familiarise yourself with the enclosed emergency fittings test record 

sheet and ensure it is completed as required and left with the end user.

Charge indicator:

Green flash when charging

Solid green when fully charged
Red indicates battery fault

Manual test button:
Press and hold to simulate 
mains power failure and 
switching to battery power, 
release button to return to 
non-maintained mode

This product has automatic self-test function. Approximately every 30 days 

it will automatically turn on the monthly check function, When in test mode, 

both LED indicators will flash red/green for approximately 30 seconds.

 

Once complete, the LED indicator will return to green if no fault is found. 

Annually(about 360 days) it will automatically turn on the annual test 

function. When in this test mode, both LED indicators will flash red/green

 

for approximately 3 hours.  If the battery power does not last for the required 

3 hours, the red of the bicolor LED will flash meaning the emergency function 

is faulty.

Ø40-45mm

Ø60

45.2

22.0

22.0

332.5

49.9

Ø38.5

Ø60

45.2

22.0

22.0

332.5

49.9

Ø38.5

Neutral: Blue
U/sw Live: Brown

Wire preparation: 0.75-1.5 

mm²

Reviews: