background image

GreenMax

®

 Distributed Room Controller

Cat. No. DRC00-0L0 

INSTALLATION INSTRUCTIONS

ENGLISH

DI-001-DRC00-02A

WARNINGS

•  

 TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR 
FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

•   To be installed and/or used in accordance with appropriate electrical codes and regulations.
•   If you are unsure about any part of these instructions, consult an electrician.

CAUTIONS

•   Use this device with 

copper or copper clad wire only.

•   For indoor applications only.
•   Save these instructions.

The GreenMax Distributed Room Controller (DRC) comes in a Line Voltage and 
Low Voltage LumaCAN™ powered product. The product manages all the energy 

PDQDJHPHQWEXVLQHVVORJLFZLWKLQDVLQJOHURRPDQGLVIXOO\VHWXSDQGFRQ¿JXUHGXVLQJ

a Wi-Fi

®

 enabled cell phone or tablet. 

•  Only one room controller should be used per room.  Each room requires one controller. 

•  The LumaCAN network can span multiple rooms and connect multiple DRC devices 

together; however it is important to pay particular attention to control and setup of rooms 
to avoid cross room control.

•  Each GreenMax DRC Controller can connect to a variety of devices, such as DRC smart 

SDFNVUHOD\SDQHOV,QWHOOHFWŒ¿[WXUHV/XPLQDŒ5)VHQVRUV'$/,GHYLFHVDQGRWKHU
GHYLFHV)RUVSHFL¿FFDSDELOLWLHVDQGFDSDFLWLHVUHIHUWRWKHSURGXFWGDWDVKHHW

Application Notes

WARNING

TO AVOID FIRE, SHOCK, OR DEATH; 

TURN OFF POWER at circuit breaker or fuse and test 
that power is off before wiring!

1.

 

Mount the controller using one of the mounting options.

NOTE: 

To remove the controller from the DIN rail, pull 

down on the tension spring and lift off.

Installation

a. 

Mounting on DIN rail

To remove 
from DIN rail

DIN rail

mounting ears

b.  

Mounting with mounting ears

Low Voltage Input

1. Pinout:

Pin 1 - Signal Input

Pin 2 - Common

Pin 3 - +24 VDC

(V follows LumaCAN supply) 

2.  Detects 0-24VDC.  Can be used as contact 

closure, 0-10V photocell input, or dry contact.

2.

 

Make all low voltage connections per the wiring diagram.

&RQ¿JXUDWLRQ

1. 

&RQ¿JXULQJWKHFRQWUROOHU

,QRUGHUWRFRQ¿JXUHDURRPZLWKWKH*UHHQ0D['5&LWLVQHFHVVDU\WRKDYHDQL26RU$QGURLG:L)LFDSDEOHGHYLFHZLWKWKH³*UHHQ0D['5&´$SSLQVWDOOHG&RQQHFWWRWKH*UHHQ0D[
'5&&RQWUROOHUDVD:L)L$FFHVVSRLQWWKHQXVHWKH$SSWRPRYHWKURXJKWKHFRQ¿JXUDWLRQSURFHVV

 

• Factory Default Access Point Name: GreenMax DRC-[serial number] (The serial number is printed on the product label, use 

only

 last four character.)

 

• Factory Default Security: WEP Security, Password: leviton0000

2. 

&KDQJLQJQHWZRUNFRQ¿JXUDWLRQ

,QVLWXDWLRQVZKHUHDZLUHOHVVDFFHVVSRLQWRUSDVVZRUGLVFKDQJHGEXWWKHFRQ¿JXUDWLRQRIWKH'5&QHHGVWRUHPDLQWKHVDPHXVHWKHIROORZLQJSURFHGXUHWRUHVHWWKHQHWZRUNDQG

reconnect to the device:

‡3UHVVDQGKROGWKH:L)LEXWWRQIRUVHFRQGVXQWLOWKH:L)L/('ÀDVKHVJUHHQUDSLGO\

 

• Release the button.  

‡7KH/('ZLOOFRQWLQXHWRÀDVKJUHHQUDSLGO\XQWLOWKHUHVHWF\FOHLVFRPSOHWH7KH/('ZLOOJRGDUNWKHQEOLQNVORZO\LQGLFDWLQJWKDWLWLVUHDG\IRUFRQQHFWLRQXVLQJLWVIDFWRU\GHIDXOW

 

AP name and credentials.  

 NOTE:

WKDWHYHQWKRXJK\RXFDQFRQQHFWWRLW\RXPXVWKDYHEHHQJUDQWHGDFFHVVE\WKHVLWHDGPLQLVWUDWRUWRXVHWKHDSSIRUFRQ¿JXUDWLRQ

3. 

LumaCAN

 

• Wire per the TIA-568B standard.

 • 

 

The sequence of network nodes, as described in the Construction Documents, 
may be critical to ensure power distribution between nodes.

 • 

 

All LumaCAN wire segments must be tested and validated prior to powering up of the system.

 • 

 

The last device in each LumaCAN run must be terminated using an RJ45 terminator plug.  
Each DRC is supplied with one terminator plug preinstalled in the smart pack.

 • 

 

Devices on LumaCAN follow daisy chain topology.  Home Run topology supported with the 
use of repeaters.  Max 110 nodes per segment, max 250 nodes per sub-net.

 

• Perform voltage drop calculations on all networks. 

To next device

From previous device

DI-001-DRC00-02A

© 2018 Leviton Mfg. Co., Inc.