WARNINGS AND CAUTIONS:

• 

DISCONNECT POWER AT CIRCUIT BREAKER OR FUSE WHEN SERVICING, INSTALLING OR REMOVING FIXTURE.

• 

DO NOT control a load in excess of the specified ratings. Damage to the unit, fire, electric shock, personal injury or death can occur. 

Check your load ratings to determine suitability for your application.

•  If you are unsure about any part of these instructions, consult an electrician.
•  To be installed and/or used in accordance with electrical codes and regulations.

WARNINGS AND CAUTIONS:

•  Do not install this unit to control a receptacle.
•  The OSSMT Vacancy Sensor is intended to replace a standard single-pole Decora wall switch.
•  Do not touch the surface of the lens. Clean outer surface with a damp cloth only.
•  Use this device 

WITH COPPER OR COPPER CLAD WIRE ONLY.

Single Pole (One Location) or Multi-Location

Multi-Technology Designer Wall Switch Vacancy Sensor

California Title 20 and 24 Compliant

Cat. No. OSSMT-TM & OSSMT-GT

Incandescent/Tungsten: 800W @ 120V     Ballast: 1200VA @ 120V     Ballast: 2700VA @ 277V     Motor: 1/4hp @ 120V

Operating Temperature Range: 0°C to 40°C

Relative Humidity: 20% to 90% non-condensing

No Minimum Load Required 

Compatible with incandescent lamps, low-voltage lighting with electronic and magnetic transformers, electronic and magnetic fluorescent ballasts, and fans.

INSTALLATION INSTRUCTIONS

 TOOLS NEEDED TO INSTALL YOUR SENSOR

Slotted/Phillips Screwdriver 

Electrical Tape 

 

Pliers 

 

 

Cutters 

 

 

Small Slotted Screwdriver

•  CEC Title 20 and 24 Compliant.
•  Manual ON/Auto OFF.
•  Leviton’s Decora

®

 design.

•  Sensor can be ganged together with other units in a multiple-switch 

wall plate.

•  Self-Adaptive Technology adjusts to occupancy patterns of use in 

auto adapt mode.

•  The Adapting Time-out walk-through feature prevents lights from 

remaining ON for an extended period after only a momentary 

occupancy.

•  Switches a single load circuit.
•  Adjustable horizontal blinders for both left and right PIR masking.
•  True Zero-Cross relay provides maximum contact life and 

compatibility with electronic ballasts.

•  Dual detection technology, both Passive Infrared and Ultrasonic. 

OSSMT-GT can be configured as Ultrasonic Only by disabling 

Passive Infrared.

•  Devices can operate in Multi-Tech or Passive Infrared Only mode.
•  Time Delay: 30 seconds to 30 minutes.
•  LED (Red/Green): Visible status indicators for determining sensing 

technology operation.

•  Vacancy Confirmation: a 30 second grace period is enabled in case 

of False OFF.

Leviton's Designer Multi-Technology Wall Switch Vacancy Sensor, Cat. 

No. OSSMT-GT/OSSMT-TM, is designed to detect motion using the 

Passive Infrared (PIR) and Ultrasonic sensor from sources (such as a 

person entering a room) within its field-of-view (monitored space). The 

Vacancy Sensor senses motion within its maximum coverage area of 

2400 sq. ft (223 m

2

). The ultrasonic (US) sensors work with the PIR 

to keep the lights ON when occupied. The controlled lights will remain 

ON until no motion is detected and the scheduled time-delay has 

expired, at which point the lights will be turned OFF. In adapting time-

out mode the sensor adapts its time delay settings to the occupancy 

patterns of a room.
The OSSMT is designed to control a single lighting control circuit and 

provide the energy savings of an vacancy sensor. The OSSMT-GT 

does not contain a neutral conductor. It is intended for use in retrofit 

applications where a neutral is not available in the wall box.
The OSSMT is a single relay device, which operates in Manual ON/

Auto OFF ONLY. 
Cat.No. OSSMT-TM is UL and cUL listed. Cat. No. OSSMT-GT is 

ETL listed and cETL listed.
The PIR tecgnology of the Vacancy Sensor uses a small semiconductor 

heat detector that resides behind a multi-zone optical lens. This Fresnel 

lens establishes dozens of zones of detection. The Sensor is sensitive 

to the heat emitted by the human body. In order to initially trigger the 

Sensor, the source of heat must move from one zone of detection to 

another. The device is most effective in sensing motion across its field-

of-view and it is less effective sensing motion towards or away from its 

field-of-view). Keep this in mind when selecting the installation location 

(refer to Field-of-View diagrams).

The Ultrasonic technology of the Vacancy Sensor uses a non-audible, high 

frequency (40kHz) sound to sense Doppler shifts caused by motion in the 

space. The US is more sensitive to small motion and does not rely on line of 

sight for detection. If both technologies have not detected any motion for the 

set timeout period, the relay and its corresponding load will be turned OFF.
Note that PIR technology responds to rapid changes in temperature, 

so care should be taken not to mount the device near a climate control 

source (i.e. radiators, air exchanges, and air conditioners). Hot or cold 

drafts will look like body motion to the device and will trigger it if the 

unit is mounted too close. 

It is recommended to mount the Vacancy 

Sensor at least 6 feet away from a climate control source.
In addition, it is also recommended NOT to mount the Vacancy Sensor 

directly under a large light source. Large wattage bulbs (greater than 

100W incandescent) give off a lot of heat and switching the bulb causes 

a temperature change that can be detected by the device. Mount the 

Vacancy Sensor at least 6 ft. away from large bulbs. If it is necessary to 

mount the device closer, lower the wattage of the bulb directly overhead.

WARNING:

 

TO AVOID FIRE, SHOCK, OR DEATH; TURN 

OFF POWER at circuit breaker or fuse and test that power is 

off before wiring!

 Step 1

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

•  Pull off pre-cut insulation from sensor leads.
•  Make sure that the ends of the wires from the wall box are 

straight 

(cut if necessary).

•  Remove insulation from each wire in the wall box as shown.

Preparing and connecting wires:

9/16"

(1.4 cm)

Strip Gage 

(measure bare 

wire here)

Cut 

(if necessary)

 Step 3

INSTALLING YOUR  SENSOR

NOTE: Use check boxes           when Steps are completed.

Installing your Sensor – Single-Pole Application:

 Step 4

Identifying your wiring application 

(most common):

 Step 2

WIRING SENSOR:

Connect wires per WIRING DIAGRAM as follows: Screw wire connector 

on clockwise making sure there are no bare conductors below the wire 

connectors. Secure each connector with electrical tape.
•  Green or bare copper wire in wall box to Green lead.
•  Line Hot wall box wire to Black lead.
•  Load wall box wire to Blue lead.
NOTE: Allow 1 minute for warm-up after connecting and energizing.

WIRING SENSOR 1:

Connect wires per WIRING DIAGRAM as follows:
•  Green or bare copper wire in wall box to Sensor 1 Green lead.
•   Line Hot (common) wall box wire identified (tagged) when removing old 

switch and First traveler from Sensor 2 to Sensor 1 Black lead.

•   Second Traveler wall box wire from Sensor 2 to Sensor 1 Blue lead.
•  For OSSMT-TM tie Neutral wires together.

WIRING SENSOR 2:

Connect wires per WIRING DIAGRAM as follows:
•  Green or bare copper wire in wall box to Sensor 2 Green lead.
•   Load wall box wire identified (tagged) when removing old switch and 

Second Traveler from Sensor 1 to Sensor 2 Blue lead.

•  First Traveler Line Hot from Sensor 1 to Sensor 2 Black lead.
NOTE: Allow 1 minute for warm-up after connecting and energizing.

 Step 5

NOTE: The Cat. No. OSSMT-GT requires a ground wire to operate 

properly. If there is no ground wire, ensure electrical box is grounded and 

attach ground wire to box with a screw. If the ground wire is floating this 

device will not work.

NOTE: The Cat. No. OSSMT-GT requires a ground wire to operate 

properly. If there is no ground wire, ensure electrical box is grounded and 

attach ground wire to box with a screw. If the ground wire is floating this 

device will not work.

NOTE: Sensor 1 must be installed in a wall box that has both a LINE Hot 

and a Ground connection. Sensor 2 

must be installed in a wall box that 

has both a Load and a Ground connection.
If you are unsure about any part of these instructions, consult an 

electrician.

NOTE: Either sensor can turn the lights ON. Both sensors must time out 

to OFF for the lights to go OFF.

 DESCRIPTION

DI-N0X-OSSMT-00A

 FEATURES

IMPORTANT: For Multi-location applications, note that one of the screw 

terminals from the old switch being removed will usually be a different 

color (Black) or labeled Common. Tag that wire with electrical tape and 

identify as the common (Line or Load) in both switch wall boxes.

NOTE: Cat. No. OSSMT-TM requires a neutral wire. If there is no neutral 

wire this device will not work.

Installing your Sensor – Multi-location Wiring 

Application:

NOTE: Dress wires with a bend as shown in diagram to relieve stress 

when mounting device.
•  Position all wires to provide room in outlet wall box for device.

•  Partially secure device using long mounting screws provided.

•  Restore power at circuit breaker or fuse.
NOTE: Allow 1 minute for warm-up after energizing.

 

 NOTE: All models of the OSSMT are factory preset to work 

without any adjustments. If necessary, adjust the Blinders and PIR 

Range Control to stop any unwanted detection of motion 

(refer to 

FEATURES section).

•   For additional Time Control Settings 

(refer to the SETTINGS 

section).

 

 NOTE: To avoid PERMANENT DAMAGE to the unit, be careful 

NOT TO OVERTURN the control knobs or levers when setting the 

Sensor. The controls can be accessed by removing the wallplate 

(if applicable) and control panel cover 

(refer to Control Panel 

Diagram). Use a small straight blade screwdriver to adjust knobs 

and blinder levers.

   NOTE: DO NOT press in on blinder levers or use excessive force 

(refer to Control Panel Diagram).

•   Attach the Control Panel cover when the desired settings are complete.

If lights do not turn ON, refer to the TROUBLESHOOTING section.

Testing your Sensor prior to completely 

mounting in wall box:

 Step 6

NOTE: To access control settings, remove the control panel cover. 

If necessary, remove the warning label that covers the adjustment 

dials (refer to Control Panel Diagram).
Factory Settings:
 The sensor is shipped from the factory to work in 

almost all situations, without any added adjustments. The factory settings 

are: Blinders open, 10 minutes fixed Time-Out, Medium passive infrared 

(PIR) range, and Medium Ultrasonic range. The PIR and ultrasonic 

technologies are both active.
Blinders: The blinders are two independent shutters that can narrow the 

field-of-view from a maximum of 180° down to 60° of arc. The blinders 

are operated by moving the blinder levers towards or away from the 

center of the Sensor. The blinder levers can be found above the control 

dials in the control panel 

(refer to Control Panel Diagram).

Time-Outs: The Sensor has three types of Time-Outs: Fixed, Adapting, 

and Walkthrough.
  •   Fixed Time-Out: The value of this Time-Out is user selected 

through the use of the Time Control Setting (refer to Control Panel 

Diagram and Time-Out Settings).

  •   

Adapting Time-Out: When activated, the value of this Time-Out 

(30 minutes) is changed by the Sensor based on room occupancy 

and lighting conditions.

  •   

Walk-through Time-Out: The value of this Time-Out is preset to 

2.5 minutes and only exists in the Adapting Time-Out mode.

 FEATURES

2

4

1

3

2

4

1

5

3

3-Way
1.  
Line or Load (See important* 

instruction)

2.  Neutral

 

NOTE: for OSSMT-TM only

3.  Ground

4.  First Traveler – note color

5.  Second Traveler – note color

Single-Pole
1.
  Line (Hot)

2.  Neutral 

NOTE: for OSSMT-TM only.

3.  Ground

4.  Load 

Black (Hot)

Neutral (White)

Load

Sensor 2

Sensor 1

OSSMT-TM Multi-Location Wiring Diagram

Black

Black

Black

White

White

Blue

White

Blue

Green

Ground

Green

Ground

Line

120-277V, 50/60Hz

Wall surface

Sensor

Mounting 

screws 

(2 places)

Note: These products are not true 3-way devices.

Black (Hot)

Neutral (White)

Load

Black

Black

White

Blue

Green

Ground

Line

120-277V, 50/60Hz

Wiring Diagram for OSSMT-GT

Black (Hot)

Neutral (White)

Load

Sensor 2

Sensor 1

Black

Black

Black

White

Blue

Blue

Green

Ground

Green

Ground

Line

120-277V, 50/60Hz

OSSMT-GT Multi-Location Wiring Diagram

White

Black (Hot)

Neutral (White)

Load

Black

Black

White

Blue

Green

Ground

Line

120-277V, 50/60Hz

Wiring Diagram for OSSMT-TM