background image

3-Way or More Applications (Multi-location)

Manual-ON Occupancy Sensor Remote

Cat. No. ACPØR-CB

120VAC, 60Hz

INSTALLATION INSTRUCTIONS

Bl

DI-000-ACP0R-00A

Tools needed to install your Remote:

Slotted/Phillips Screwdriver 

Electrical Tape 

Pliers 

Pencil 

Cutters 

Ruler

INSTALLING YOUR REMOTE

NOTE: 

Use check boxes       when Steps are completed.

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

/.

/&&

3

5

1
2

6

4

4-Way

1. 

First Traveler – note color

 

2. 

Second Traveler – tagged

 

3. 

Neutral

 

4. 

Ground

 

5. 

Third Traveler – note color

 

6. 

Fourth Traveler – tagged 

NOTE:

 For matching remote 

w/LEDs installation, the 

First

 

Traveler

 becomes Line Hot.

 Step 1

 Step 2

Step 3

Cut

(if necessary)

Side Wire Connection

Side wire terminals accept 

#14 AWG 

solid copper wire only.

Back Wire (either hole may 

be used)

Back wire openings use #14-12 

AWG 

solid copper wire only.

•   Make sure that the ends of the wires from the wall box are 

straight (cut if necessary)

.

•  Remove insulation from each wire in the wall box as shown.

WARNINGS AND CAUTIONS:

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  If you are unsure about any part of these instructions, consult a qualified electrician.
•   To avoid overheating and possible damage to this device and other equipment, do not install to control a receptacle, fluorescent lighting, a motor- or a transformer 

operated appliance.

•  Acenti™ sensors are not compatible with standard 3-way or 4-way switches. They must be used with compatible Acenti™ remotes for multi-location operation.

WARNINGS AND CAUTIONS:

•  Recommended minimum wall box depth is 2-1/2”.
•  Maximum wire length from sensor to all installed remotes cannot exceed 300 ft.
•  Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture.
•  Use this device only with copper or copper clad wire. With aluminum wire use only devices marked CO/ALR or CU/AL.

Strip Gage (measure 

bare wire here or use 

gage on back of the 

sensor)

5/8”

(1.6 cm)

5/8”

(1.6 cm)

Important Notice for Installer

To achieve proper aesthetic installation of the Acenti products, 

the wall surface surrounding the wall box opening must be 

fairly flat and free of irregularities. The wall box must be 

level and recessed or flush to the wall surface. The Acenti 

installation system allows for adjustments that will correct 

minor flaws that may be present in the installation area.
This device must be installed with the Acenti™ Alignment 

Plate. The Alignment Plate is packaged with the Acenti™ 

Wallplate, which is sold separately from this device.
The Alignment Plate will function properly only if it is mounted 

to a flat wall surface as described above.

   Leviton recommends to temporarily position the Alignment Plate 

prior to wiring the device. If the wall box wires extend at least 

6 inches out of the wall box, it is also possible to install the 

Alignment Plate after the device has been wired 

(refer to Wallplate 

instruction sheet)

.

•   

The Alignment Plate must be installed with the tab towards the 

bottom.

•   

Leviton recommends the following 3 methods to 

temporarily

 hold 

the Alignment Plate – use of device mounting screw, use of wall box 

wires, or use of electrical tape 

(refer to the following figures)

:

Installing your Alignment Plate:

 Step 4

2

4

1

5

3

3-Way

1. 

Line or Load

 (See important 

  instruction below)

 

2. 

Neutral

 

3. 

Ground

 

4. 

First Traveler – note color

 

5. 

Second Traveler – note color 

NOTE:

 For matching remote 

w/LEDs installation, the 

First

 

Traveler

 becomes Line Hot.

 Step 3 cont’d

Preparing and connecting wires:

This remote can be wired using side wire terminal screws 

or through backwire openings. Choose appropriate wire 

stripping specifications accordingly.

Strip Gage (measure 

bare wire here or use 

gage on back of the 

sensor)

Alignment Plate 

Held By Tape

Alignment Plate 

Held By Wires

Alignment Plate Held 

By Mounting Screw

TOP

Mounting

Screw

Alignment

Plate

TOP

TOP

Electrical

Tape

3-Way Wiring with ACPØR Remote 

Application:

 Step 5a

Hot (Bla c k ) 

Neutral (White) 

Sensor 

ACP0R/AC0SR-1L Remote 

YL/RD 

RD 

YL/RD 

WH 

BK 

BK 

Bla c k 

White

Line  

120 V A C ,  60H z 

WH 

Load 

Green 

Ground 

Green 

Ground 

Bk

WH

YL/RD RD

Bk

WH

YL/RD RD

Bk

WH

YL/RD RD

4

3

2

1

5

Additional

Neutral Wire

ACPØR Remote

(3-Way Wall box from Step 2)

ACPØR Remote

(4-Way Wall box from Step 2)

Sensor

(3-Way Wall box from Step 2)

4

4

3

3

5

5

1

2

Additional

Neutral Wire

Terminal

Screw

marked

Yellow/Red

(YL/RD)

Terminal

Screw

marked

Black (Bk)

Terminal

Screw

marked

Yellow/Red

(YL/RD)

Terminal

Screw

marked

Black (Bk)

Terminal

Screw marked

White (WH)

Terminal

Screw marked

White (WH)

6

2

1

Terminal Screw marked
White (WH)

2

NOTE: 

The sensor 

must

 be installed in a wall box that has a Load 

connection. The remote 

must

 be installed in a wall box with a Line 

Hot connection and a Neutral connection. A neutral wire to the remote 

needs to be added as shown.
If you are unsure about any part of these instructions, consult a 

qualified electrician. 

NOTE:

 Maximum wire length from sensor to all installed remotes 

cannot exceed 300 ft.

WIRING ACPØR REMOTE (wall box with Line Hot 

connection):
Connect wires per WIRING DIAGRAM as follows:

  Green or bare copper wire in wall box to Green terminal screw.

•   

Line Hot (common) wall box wire identified (tagged) when removing 

old switch and First Traveler to sensor terminal screw marked “BK”.

•   

Second Traveler wall box wire from ACP15 sensor to remote 

terminal screw marked “YL/RD” 

(note wire color)

. This traveler 

must go to the terminal screw on the sensor marked “YL/RD”.

• 

Line Neutral wall box to remote terminal screw marked “WH”.

WIRING ACP15 SENSOR (wall box with Load connection):
Connect wires per WIRING DIAGRAM as follows:

   Green or bare copper wire in wall box to Green terminal screw or 

Green sensor lead.

•   

Load wall box wire identified (tagged) when removing old switch to 

sensor terminal screw marked “RD” or the Red sensor lead.

•   

First Traveler Line Hot to sensor terminal screw marked “BK”.

•   

Remove Red insulating label from terminal screw marked “YL/RD”.

•   

Second Traveler wall box wire 

(note color as above)

 to sensor 

terminal screw marked “YL/RD”. This traveler from the sensor must 

go to the terminal screw on the remote marked “YL/RD”.

• 

Line Neutral wall box to sensor terminal screw marked “WH”.

•  Proceed to Step 6.

4-Way Wiring with ACPØR Remote 

Application:

 Step 5b

Hot (Black)

Neutral (White)

Load

Sensor

ACPØR Remote

ACPØR Remote

YL/
RD

YL/RD

YL/RD

RD

WH

WH

WH

Bk

Bk

Bk

Black

White

Line 

120vAC, 60Hz

Green

Ground

Green

Ground

Green

Ground

Bk 

WH 

YL/RD RD

 

Bk 

WH 

YL/RD RD

 

A d ditiona l 

Neutral  W ir e 

T ermina l 

Scr e w marke d  

 

Bla c k (Bk ) 

T ermina l 

Scr e w marke d  

 

Y ell o w/Re d  

 

(YL/RD) 

T ermina l 

Scr e w marke d  

 

Red (RD) 

T ermina l 

Scr e w marke d  

 

White (WH) 

Sensor 

ACP0R Remote

WARNING:

 

TO AvOID FIRE, SHOCk, OR DEATH; 

TURN OFF POWER

 at circuit breaker or fuse and test 

that power is off before wiring!

Identifying your wiring application (most 

common):

NOTE:

 If the wiring in the wall box does not resemble 

any of these configurations, consult a qualified electrician.

NOTE: 

The sensor 

must

 be installed in a wall box that has a Load 

connection. The remote 

must

 be installed in a wall box with a Line 

Hot connection and a Neutral connection. A neutral wire to the remote 

needs to be added as shown.
If you are unsure about any part of these instructions, consult a 

qualified electrician.

NOTE:

 Maximum wire length from sensor to all installed remotes 

cannot exceed 300 ft.

WIRING ACPØR REMOTE (4-Way wall box with Line Hot 

connection):
Connect wires per WIRING DIAGRAM as follows:

  Green or bare copper wire in wall box to Green terminal screw.

•   

First Traveler and Third Traveler wall box wire from sensor in the 

3-way box to remote terminal screw marked “BK” in the 4-way box, 

and to the terminal screw marked “BK” of the remaining remote in 

the 3-way box.

•   

Second Traveler 

(tagged)

 and Fourth Traveler 

(tagged)

 wall box 

wire from sensor

 

in the 3-way box to remote terminal screw marked 

“YL/RD” in the 4-way box, and to the terminal screw marked “YL/RD” 

of the remaining remote in the 3-way box

 (note wire colors)

This traveler from the remotes must go to the terminal screw on the 

sensor marked “YL/RD” or the Yellow/Red sensor lead.

• 

Line Neutral wall box wire to remote terminal screw marked “WH”.

WIRING ACPØR REMOTE (3-Way wall box with Line Hot 

connection):
Connect wires per WIRING DIAGRAM as follows: 

  Green or bare copper wire in wall box to Green terminal screw.

•   

Line Hot (common) wall box wire identified (tagged) when removing 

old switch and First Traveler to sensor terminal screw marked “BK” 

or the Black sensor lead.

•   

Second Traveler wall box wire from sensor to remote terminal screw 

marked “YL/RD” 

(note wire color as above)

. This traveler from 

the remote must go to the terminal screw on the sensor marked 

“YL/RD” or the Yellow/Red sensor lead.

• 

Line Neutral wall box wire to remote terminal screw marked “WH”.

WIRING SENSOR (3-Way wall box with Load connection):
Connect wires per WIRING DIAGRAM as follows:

   Green or bare copper wire in wall box to Green terminal screw or 

Green sensor lead.

•   

Load wall box wire identified (tagged) when removing old switch to 

sensor terminal screw marked “RD” or the Red sensor lead.

•   

First Traveler Line Hot to sensor terminal screw marked “BK” or the 

Black sensor lead.

•   

Remove Red insulating label from terminal screw marked “YL/RD” 

or the Yellow/Red sensor lead.

•   

Second Traveler wall box wire 

(note color as above)

 to sensor 

terminal screw marked “YL/RD” or the Yellow/Red sensor lead. 

This traveler from the sensor must go to the terminal screw on the 

remote marked “YL/RD”.

• 

Line Neutral wall box to sensor terminal screw marked “WH”.

•  Proceed to Step 6.

IMPORTANT:

For 3-Way applications

, note that one of the screw terminals from 

the old switch being removed will usually be a different color (Black) 

or labeled Common. Tag that wire with electrical tape and identify as 

the common (Line or Load) in both the sensor wall box and remote 

wall box.

For 4-Way applications

, note that the old switch being removed will 

have 4 screws plus a ground screw. Tag the two same color insulated 

wires with electrical tape.

 Step 5c

3-Way Wiring with Acenti Dimmer without 

Neutral Connection:

NOTE:

 The dimmer 

must

 be installed in a wall box that has a Load 

connection. The sensor remote 

must

 be installed in a wall box with 

a Line Hot connection and a Neutral connection. A Neutral wire to 

the matching remote needs to be added as shown.
If you are unsure about any part of these instructions, consult a 

qualified electrician.

NOTE:

 Maximum wire length from sensor to all installed remotes 

cannot exceed 300 ft (90 m).

WIRING SENSOR REMOTE

 

(wall box with Line Hot 

connection):

Connect wires per WIRING DIAGRAM as follows:

•   Green or bare copper wire in wall box to Green terminal screw.

•   Line Hot (common) wall box wire identified (tagged) when 

removing old switch and First Traveler to dimmer terminal screw 

marked “BK”.

•   Second Traveler wall box wire from sensor to remote terminal 

screw marked “YL/RD” 

(note wire color)

. This traveler from 

the remote must go to the terminal screw on the sensor marked 

“YL/RD”.

•   Line Neutral wall box wire to remote terminal screw marked 

“WH”.

WIRING DIMMER

 

(wall box with Load connection):

Connect wires per WIRING DIAGRAM as follows:

•   Green or bare copper wire in wall box to Green terminal screw.

•   Load wall box wire identified (tagged) when removing old switch 

to terminal screw marked “RD”.

•   First Traveler Line Hot to terminal screw marked “BK”.

•   Remove Red insulating label from terminal screw marked 

“YL/RD”.

•   Second Traveler wall box wire 

(note color as above)

 to terminal 

screw marked “YL/RD”. This traveler from the dimmer must go 

to the terminal screw on the remote marked “YL/RD”.

•   

Proceed to Step 6.

BK

YL/RD RD

BK

WH

YL/RD RD

Additional

Neutral Wire

Terminal

Screw marked

Black (BK)

Terminal

Screw marked

Yellow/Red

(YL/RD)

4

3

5

1

2

3

1

4

5

Terminal

Screw marked

Red (RD)

Dimmer

Sensor Remote

Hot (Black)

Neutral (White)

Dimmer

Sensor Remote (with LEDs)

RD

YL/RD

YL/RD

BK

BK

Line 

120VAC, 60Hz

Green
Ground

Green

Ground

WH

Black

White

Load