Leviton 51120-1 Quick Start Manual Download Page 1

INSTALLATION

WARNINGS & CAUTIONS:

•  TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH ELECTRICAL CODES AND REGULATIONS.

•  INSTALLATION OF CAT. NOS. 51120-1 AND 51120-3 SPD DEVICES IN A BRANCH CIRCUIT MUST BE DONE BY AN ELECTRICIAN.

•  READ ALL INSTRUCTIONS BEFORE INSTALLING.

•  CAT. NOS. 51120-1 AND 51120-3 SPD DEVICES MUST BE INSTALLED ON A LINE THAT IS SERVED BY DISCONNECT MEANS, SUCH AS 20-AMP CIRCUIT BREAKERS OR 20-AMP 

FUSED DISCONNECT SWITCHES.

•  SPD MAY NOT SURVIVE SUSTAINED OVERVOLTAGES.

•  USE THIS DEVICE 

ONLY WITH COPPER OR COPPER CLAD WIRE.

FEATURES:

•  UL 1449 Listed - Type 2 SPD

•  IEEE C62.41-1991 category A&B combination wave suppression

•  Solid-state semiconductor SPD circuitry for each phase

•  Each phase independently fused

•  Green LED diagnostic indicator for each phase

•  NEMA 1 metal enclosure

•  Pre-punched standard knockouts

•  Interior plastic circuit enclosure for added safety

•  Flush mounting enclosure
For superior local SPD protection, use Leviton Surge Suppression Outlets to protect against internally-generated transients between the branch panel and the point of use.

DESCRIPTION:

Leviton’s Catalog Nos. 51120-1 (120/240V, single -phase version) and the 51120-3 (120/208V, 3-phase version) Branch Panel Mounted SPD devices have been designed to protect 

residential and small commercial establishments from high voltage transients. The standard J-Box metal enclosure with pre-punched standard size knockouts simplifies flush 

mounting in typical frame construction environments, and provides convenient connection means to existing branch panels.

TO INSTALL:

System Voltage Requirements

1.

  Measure panel voltage, L-N, to determine the system voltage. System voltage must not exceed the specified maximum continuous RMS voltage on the SPD device label.

Location and Mounting

1.

  Locate the SPD device as close as possible to the branch circuit breaker panel. Connection lead length between the SPD device and circuit breaker box should be minimal for 

best protection. The location should also permit good visibility of the SPD device’s diagnostic lights.

2.

  Remove the circuit breaker panel cover and determine the breaker-panel wiring entry point relative to chosen location of the SPD device.

 

NOTE:

 Since the circuit breaker panel and the SPD unit have overlapping covers, installation should allow at least one inch of clearance from the edge of the circuit breaker 

panel cover.

3.

  For surface-mount circuit breaker panels, the SPD device may be connected using rigid conduit to any conduit knockout hole.

4.

  For non-surface mount installations, secure the SPD to the support stud in the wall by cutting a 6 x 6-inch mounting hole.

5.

  Remove SPD’s cover and connect 3/4-inch flexible or rigid conduit between circuit breaker box and the SPD.

6.

  Place the SPD device into the 6 x 6-inch mounting hole and secure it to the exposed studs.

Wiring Connections

The SPD device terminal block accepts 4 AWG – 12 AWG COPPER WIRE ONLY. For wire range Solid or Stranded 12 AWG to 10 AWG use Torque 25 in-lbs. For 8 AWG Stranded 

wire use 30 in-lbs. For Stranded 6 AWG – 4 AWG use 35 in-lbs.

1.

 

WARNING:

 TO AVOID FIRE, SHOCK OR DEATH, 

TURN OFF POWER

 AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

2.

  Connect wire leads to terminal block: BLACK to PHASES, WHITE to NEUTRAL and GREEN to GROUND. See 

Figures 1

 through 

4

 on reverse side.

  CAUTION:

 If plastic conduit is used, Green ground wire must be connected to ground lug, and Green wire inside enclosure must also be connected to ground lug. Failure to do 

so may result in fire or shock. See 

Fig. 1

Fig. 2

Fig. 3

 and 

Fig. 4

 on reverse side for installation diagrams.

3.

  Thread the SPD device’s wire leads through the conduit to circuit breaker interior.

4.

  Secure the SPD cover with the screws removed previously.

5.

  Select circuit breakers as close as possible to each service entrance lug. Twenty-Amp (20A) circuit breakers are recommended, and may share SPD device and branch circuit 

leads. The breakers provide additional failure protection as well as a SPD connection and servicing disconnect.

  NOTE:

 Do not connect SPD leads directly to service entrance lugs. This may result in fire, shock or death.

6.

  Lead lengths should be as short as possible. Connect the BLACK leads to each PHASE through the selected circuit breakers. Connect the WHITE lead to NEUTRAL as close as 

possible to NEUTRAL entrance service lug.

  NOTE: 

Avoid long loops and do not coil extra lead wire.

7.

  Replace the circuit breaker panel cover. Installation is complete.

Power ON

1.

  Restore power to circuit breaker panel. The green diagnostic lights on the SPD device should turn ON.

2.

  If during normal operation a diagnostic light shuts off, have an electrician determine if phase power is applied. If power is present, then a transient surge has exceeded the SPD 

device’s rating. The unit should be replaced and/or upgraded as soon as possible.

BRANCH PANEL MOUNTED SURGE PROTECTIVE DEVICE (SPD)

Cat. Nos. 

51120-1 & 51120-3

DI-000-51120-00E