WARNINGS & CAUTIONS:

•  TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT 

THE POWER IS OFF BEFORE WIRING OR WORKING ON A SPD DEVICE!

•  TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH ELECTRICAL CODES AND REGULATIONS.

•  IF YOU ARE NOT SURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONSULT AN ELECTRICIAN.

•  THIS DEVICE IS NOT A LIGHTNING ARRESTER, AND WILL NOT SURVIVE LIGHTNING STRIKES IN CLOSE 

PROXIMITY TO THE PREMISES OR SUSTAINED OVERVOLTAGES.

•  THIS DEVICE IS DESIGNED FOR USE IN EQUIPMENT OR INSTALLATIONS REQUIRING A PERMANENT 

HARD-WIRED DEVICE.

•  FOR 51015-WM ONLY – THIS DEVICE MUST NEVER BE INSTALLED ON A LINE THAT IS NOT SERVED BY 

DISCONNECT MEANS, SUCH AS 15-AMP CIRCUIT BREAKERS OR 15-AMP FUSED DISCONNECT SWITCHES.

•  FOR 51020-WM ONLY – THIS DEVICE MUST NEVER BE INSTALLED ON A LINE THAT IS NOT SERVED BY 

DISCONNECT MEANS, SUCH AS 20-AMP CIRCUIT BREAKERS OR 20-AMP FUSED DISCONNECT SWITCHES 

•  OPERATE INDOORS BETWEEN 30-90% RELATIVE HUMIDITY.

•  USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE.

INTRODUCTION

Transient voltage surges are short-term deviations from a desired voltage level or signal that can occur at any time. 

Such changes can result in an electronic device malfunction or cause extensive damage. Also termed “spikes”, these 

occurrences take place as a result of magnetic field/inductive coupling or whenever the line current is interrupted. They 

can originate from either inside a facility or derive from outside utility lines. Sources within a facility involve loads that are 

switched, such as electric motors that are turned ON and OFF. Outside transient influences involve utility grid switching.

DESCRIPTION

Leviton's Wired Modules, Cat. Nos. 51015-WM, 51020-WM and 51020-DIN, are ideally suited for use by Original 

Equipment Manufacturers (OEM’s) who wish to provide superior SPD protection for their equipment.

FEATURES

•  cURus Type 4 SPD.

•   IEEE C62.41-1991 category A&B combination wave and ringwave suppression.

•  Three protection modes – L-N, L-G, N-G.

•  Two suppression stages – primary and backup.

•  Fused for suppression protection failure.

•  EMI/RFI filtration circuitry.

•   Three diagnostic modes include LED indicators for phase-neutral polarity reversal, open ground and suppression 

failure. Suppression failure also has an audible indicator.

•  48-62 Hz operation.

•  Location per IEC std: Class III.

•  One port.

TO INSTALL

System Voltage and Current Requirements:

1.   Determine the system voltage of the equipment to be protected. The Wired Modules are rated for 120V single phase 

line-to-neutral with a ground return.

2.  Determine the current rating of the equipment to be connected.

3.  The Wired Modules are series connected devices. Cat. No. 51015-WM is rated for 15 Amp maximum load. Cat. No. 

51020-WM is rated for 16 Amp maximum load. Be aware of the line and load side designations. 

4.  The line side (power input) has two terminals: L-Line in and N-Neutral in.

5.  The load side (power output) has two terminals: L-Line out and N-Neutral out.

6.  Line and Load side terminal blocks should use #12-#8 AWG wires, secured to terminals using 12 in.-lbs. of torque. 

The grounding terminal block is suitable for use with #14-#10 AWG copper wire when torqued to 35 in.-lbs., and is 

suitable for use with #8-#6 AWG copper wire when torqued to 45 in.-lbs.

7.   There is a single-point ground terminal located on the top side of the housing. All input and output ground connections 

must be made at this terminal.

8.  Connect the Wired Modules as follows: Figure 2 shows a single phase line-to-neutral installation of Cat. No. 

51020-WM. Figure 3 shows a 3 phase line-to-neutral installation utilizing three Cat. No. 51020-WMs.

9.   Assembly (51020-DIN): Enclosed DIN clip hardware may be used to mount the module on its side using a DIN rail, 

as shown in Figure 1.

10.  51020-DIN should be pushed gently into place onto a DIN rail. This module will attach to a 35 mm standard DIN Rail 

(DIN EN 50022) or a (32 mm "G" DIN Rail (DIN EN 50035).

Power ON Diagnostics:

1.  Turn power ON and check the diagnostic lights. If the Module is properly installed and the system wiring is correct, 

the Green ground LED will be lit. This signifies that power is ON and ground continuity exists between the protected 

equipment and the building power source.

2.   If the power is OFF, the Green ground LED and the Red polarity LED will be OFF. 

3.   If power is present and the Red polarity LED is lit, but the Green ground LED is OFF, it signifies that power is present 

but Hot and Neutral wiring is reversed in polarity or an open ground condition exists. This could be due to a reversal 

somewhere in the building wiring, an open ground or an error in the Wired Module connections. 

  NOTE: THIS IS A POTENTIALLY UNSAFE CONDITION AND SHOULD BE CORRECTED IMMEDIATELY.

4.   Relay status circuit and contacts are rated at 5 Amps. The voltage rating is 250VAC/30VDC. Contacts accomodate 

#20-#12 AWG wire secured to terminals using 3.5 lb.-in. of torque. If both primary and secondary surge suppression 

fail, continuity will be between the “NO” and “C”.

Surge Protection Diagnostics:

The Wired Modules include two levels of surge protection: primary and backup. Illuminated Red LEDs and an audible 

tone indicate surge suppression failure has occurred. The audible tone provides failure warning when the Wired Module 

is contained within a piece of equipment and the LEDs are not readily visible.

1.   Unlit RED LEDs and absence of audible tone indicate primary and backup surge protection circuitry is in working 

order. 

2.  If either one of the RED Protection LED’s are lit and there is an audible tone, it signifies loss of either primary or 

backup protection. Backup surge suppression can be relied on temporarily, but the Wired Module should be replaced 

as soon as possible.

3.   If both RED Protection LEDs are lit and there is an audible tone, all surge protection has failed, but power will 

continue to be applied to the load. If either step 2 or step 3 has occured, a transient surge has exceeded the rating of 

the Wired Modules and they should be replaced immediately.

  NOTE: THIS IS A POTENTIALLY UNSAFE CONDITION AND SHOULD BE CORRECTED IMMEDIATELY.

Wired Modules

Cat. Nos. 51015-WM; Rated: 15A-120V

51020-WM; Rated: 16A-120V

51020-DIN; Rated: 16A-120V

INSTALLATION

English

PK-93730-10-02-0B

Figure 1 – 51020-DIN Installation

Figure 1 – Installation du 51020-DIN

Figure 1 – Instalación del 51020-DIN

Wired Module

Module câblé

Módulo Cableado 

(

4) #10-32 Screws

Vis 10-32 (4)

Tornillos #12-32 (4)

(4) Washers

Rondelles (4)

Arandelas (4)

DIN Rail Clip

Agrafe pour rails DIN

Gancho de riel DIN

(4) #10-32 Nuts

Écrous 10-32 (4)

Tuercas #10-32 (4)

Figure 2 – Single Phase, Line-to-Neutral installation of a 51020-WM Wired Module.

Figure 2 – Installation monophasée « ligne à neutre » d’un module 51020-WM.

Figura 2 – Instalación Línea a Neutro de Fase Sencilla del módulo cableado 51020-WM.

L

N
G

Line In

Entrée de Ligne

Entrada de Línea

L

N

CB

L

N

Load

Charge 

Carga

L

N

To Load

Vers les

charges

A carga

Cat. No. 

51020-WM

120V

From Line

De la source

d’alimentation

De la línea 

NC C NO

Relay Status Contacts

Contacts d’état

des relais

Contactos del estado

del relevador

NOTE: Cat. No. 51015-WM & 51020-DIN Wired Module installation is similar.

REMARQUE : l’installation du modèle 51015-WM et 51020-DIN est similaire.

NOTA: La instalación del Módulo No. de Cat. 51015-WM y 51020-DIN es similar.

NOTE: Cat. No. 51015-WM & 51020-DIN Wired Module installation is similar.

REMARQUE : l’installation du modèle 51015-WM et 51020-DIN est similaire.

NOTA: La instalación del Módulo No. de Cat. 51015-WM y 51020-DIN es similar.

Figure 3 – Three Phase, Line-to-Neutral installation using three 51020-WM Wired Modules.

Figure 3 – Installation triphasée « ligne à neutre » de trois modules 51020-WM.

Figura 3 – Instalación Línea a Neutro, de Tres Fases, usando tres módulos cableados 51020-WM

L

N

G

L1

L2

L

N

Cat. No. 

51020-WM

120V

SPD Module 1 (L1- N)

Module DLST 1 (L1-N)

Módulo PSTT 1 (L1-N)

L

N

G

L1

L2

L

N

Cat. No. 

51020-WM

120V

L

N

G

L1

L2

L

N

Cat. No. 

51020-WM

120V

L1

L2

CB

CB

L3

CB

N

From Line

De la source

d’alimentation

De la línea 

Load

Charge 

Carga

Load 1

Charge 1

Carga 1

Load 2

Charge 2

Carga 2

Load 3

Charge 3

Carga 3

Line In

Entrée de Ligne

Entrada de Línea

SPD Module 2 (L2- N)

Module DLST 2 (L2-N)

Módulo PSTT 2 (L2-N)

SPD Module 3 (L3- N)

Module DLST 3 (L3-N)

Módulo PSTT 3 (L3-N)

Load

Charge 

Carga

Line In

Entrée de Ligne

Entrada de Línea

Load

Charge 

Carga

Line In

Entrée de Ligne

Entrada de Línea

For Technical Assistance Call:

1-800-824-3005 (U.S.A. Only)

1 800 405-5320 (Canada Only)

www.leviton.com

LIMITED 10 YEAR WARRANTY AND EXCLUSIONS

Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for 10 years from 

the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if within such 10 year period the product is returned prepaid, with proof of purchase date, and a description of the problem to 

Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, New York 11747. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. 

This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any 

labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any 

such implied warranty, including merchantability and fitness for a particular purpose, is limited to 10 years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or 

loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

Reviews: