Starting up the device - IO-Link interface
Leuze electronic
CML 730-PS
81
NOTICE
Perform teach after changing the blanking configuration!
Perform a teach after changing the blanking configuration.
A teach can be performed via the receiver control panel or via the teach command.
Parameter
Index
Sub-
index
Data type
Access Value range
Default Explanation
Blanking settings
76
0
record
208 bit
RW
Number of auto-blanking
areas
76
1
(bit
offset
= 200)
unsigned 8
RW
0 … 4
0
Permissible number of auto blanking areas
0: 0 auto blanking areas
1: 1 auto blanking area
2: 2 auto blanking areas
3: 3 auto blanking areas
4: 4 auto blanking areas
Auto blanking (during
teaching)
76
2
(bit
offset
= 192)
unsigned 8
RW
0 … 1
0
0: Not active (only manual configuration possible)
1: Active (blanking areas autom. configured by
teach)
Logical value for blanking
area 1
76
3
(bit
offset
= 176)
unsigned 16
RW
0 … 4
0
0: No beams blanked
1: Logical value 0 for blanked beams
2: Logical value 1 for blanked beams
3: Logical value = same as neighbor beam with
lower beam number
4: Logical value = same as neighbor beam with
higher beam number
Start beam of blanking
area 1
76
4
(bit
offset
= 160)
unsigned 16
RW
1 … 1774
1
End beam of blanking
area 1
76
5
(bit
offset
= 160)
unsigned 16
RW
1 … 1774
1
Logical value for blanking
area 2
76
6
(bit
offset
= 128)
unsigned 16
RW
0 … 4
0
0: No beams blanked
1: Logical value 0 for blanked beams
2: Logical value 1 for blanked beams
3: Logical value = same as neighbor beam with
lower beam number
4: Logical value = same as neighbor beam with
higher beam number
Start beam of blanking
area 2
76
7
(bit
offset
= 112)
unsigned 16
RW
1 … 1774
1
End beam of blanking
area 2
76
8
(bit
offset
= 96)
unsigned 16
RW
1 … 1774
1
......
....
....
..
..
..
.......
......
....
....
..
..
..
.......
Logical value for blanking
area 4
76
12
(bit
offset
= 32)
unsigned 16
RW
0 … 4
0
0: No beams blanked
1: Logical value 0 for blanked beams
2: Logical value 1 for blanked beams
3: Logical value = same as neighbor beam with
lower beam number
4: Logical value = same as neighbor beam with
higher beam number
Start beam of blanking
area 4
76
13
(bit
offset
= 16)
unsigned 16
RW
1 … 1774
1
End beam of blanking
area 4
76
14
(bit
offset
= 0)
unsigned 16
RW
1 … 1774
1