Starting up the device - Basic configuration
Leuze electronic
CML 730-PS
63
Select Main Settings > Sensitivity Setting > Function Reserve
For the switching threshold, enter a value between 10% (lowest sensitivity) and 98% (highest sensi
-
tivity). Factory setting: 75%
For the detection of transparent objects, a switching threshold setting of 75% … 85% is recommended.
For the hysteresis, enter a value for the reactivation threshold after switching (5% … 80%). This
smooths any bounce around a limit value.
Target function reserve
The structure of the configuration in the receiver control panel menu is as follows:
Select Main Settings > Sensitivity Setting > Function Reserve > Target Function Reserve
The nominal value describes the value of the light quantity which is to reach the receiver. Enter a value
between 1 (smallest light quantity) and 999 (largest light quantity). Factory setting: 999
For the switching threshold, enter a value between 10% (lowest sensitivity) and 98% (highest sensi
-
tivity). Factory setting: 75%
The upper switch-on threshold of the light curtain is defined using the switching threshold. The switch-
off threshold is calculated as follows:
switch-off threshold = switching threshold - hysteresis
For the hysteresis, enter a value for the reactivation threshold after switching (5% … 80%). This
smooths any bounce around a limit value.
Example: Switching threshold: 75%; hysteresis: 10%. The light curtain switches off when 65% of the
light quantity configured as the nominal value reaches the receiver. The light curtain switches on again
when 75% of the light quantity configured as the nominal value reaches the receiver.
Level 0
Level 1
Level 2
Description
Main
Settings
Commands
Operation
Settings
Sensitivity
Setting
Function
Reserve
High
Medium
Low
Transparent
Target Func.
Res.
Tx/Rx Power
Switch
Threshold
10 … 98
Hysteresis
5 … 80
The adjustment options
Nominal value
,
Transmitting power
and
Receiver sensitivity
have no
function in the function reserve modes
High
,
Medium
,
Low
and
Transparent
. These settings are
only effective when configuring the function reserve modes
Target function reserve
and
Tx/Rx power
.
Level 0
Level 1
Level 2
Description
Main
Settings
Commands
Operation
Settings
Sensitivity
Setting
Function
Reserve
High
Medium
Low
Transparent
Target Func.
Res.
Tx/Rx Power
Nominal Value
1 … 999
Switch
Threshold
10 … 98
Hysteresis
5 … 80