Commissioning and configuration
Leuze electronic GmbH + Co. KG
BCL 358
i
105
Figure 10.15: Configuration of example 4 - module definition with the EDS file
Structure of input assembly 100
Structure of output assembly 121
Structure of configuration assembly 190
Since the configuration is not used, the length of the configuration assembly is specified as 0. The device
then operates with the default values. In this case, the acknowledge mode is not used.
Inst.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
100
0
Device status
1
Number of results
2
Reserved
Waiting for
acknowledg
-
ment
New result
(toggle bit)
Buffer over
-
flow
Further
results in the
buffer
User data or
command
Status
activation
3
Result data length (low byte)
4
Result data length (high byte)
5
Data Byte 0
6
Data Byte 1
…
…
32
Data Byte 27
Inst.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
121
0
Reserved
Standby
Error
acknowl
-
edge
Data
reset
Data
acknowledg
-
ment
Activation
signal
1
Fragment number (see chapter 10.7.6 "Class 108 - Entry data")
2
Remaining fragments (see chapter 10.7.6 "Class 108 - Entry data")
3
Fragment size (see chapter 10.7.6 "Class 108 - Entry data")
4
Reserved
New
entry
(toggle bit)
New
data
5
Entry data length (low byte)
6
Entry data length (high byte)
7
Data Byte 0
8
Data Byte 1
9
Data Byte 2