Safety field interruption:
The safety outputs of the TNT 35/7-24V are opened (LED "OFF/ON" on red) if during
safety operation the light beam of the protective photo electric sensor is interrupted.
The restart-disable inside the TNT 35/7-24V becomes active and prevents an automatic
restart of the machine. The yellow LED "Start" displays the function of the restart-disable.
The TNT 35/7-24V is in waiting state and can be restarted by pressing the start-/restart
button after the safety field is free.
5.6
Fault indication and device reset
Faults of the test monitoring unit TNT 35/7-24 are indicated by the blinking of the red "ON/
OFF" LED. The possible faults are:
Fault in the operating mode selection:
The selected operating mode of the device at startup (with/without start- and restart-
disable) changed during operation. The jumper (terminal 22 to terminal 23 or terminal 23 to
terminal 24) should be checked that it is set to the desired operating mode.
Fault in the relay monitoring:
A fault in the wiring or soldered safety contacts was detected by the TNT 35/7-24. The
wiring and connected contacts should be checked.
Internal device failures:
Equipment faults that are caused by an internal defect result in the unit going into locked
state.
Figure 5.5-4:
Display of the TNT 35/7-24V during a safety field interruption