Electrical connection
Leuze electronic
IPS 208i
33
Function as switching output
18-
30 V
D
C
SWO (Pin 4, 7-10)
VIN (Pin 1)
VIN
GNDIN (Pin 2)
max. 60 mA
2
1
1
Switching output
2
Switching output from controller
Fig. 7.4:
Switching output SWO2, SWO5 … SWO8 connection
NOTICE
Maximum loading of the switching outputs!
Ä
Do not load the respective switching output of the sensor with more than 60 mA at
+18 V … +30 V DC in normal operation.
Ä
Each configured switching output is short-circuit proof.
7.3
HOST - Host input / Ethernet
4-pin, M12 socket (D-coded) for connecting to HOST.
1
3
2
4
Fig. 7.5:
HOST connection
Tab. 7.2:
HOST pin assignment
Pin/terminal
Designation
Assignment
1
TD+
Transmit Data +
2
RD+
Receive Data +
3
TD-
Transmit Data -
4
RD-
Receive Data -
Thread (M12
socket)
FE (functional earth)
Connection cable shield.
The shield of the connection cable is on the thread of the
M12 socket.
NOTICE
Use ready-made cables!
Ä