Starting up the device - CANopen interface
Leuze electronic
CML 720i Ex
88
Blanking settings (group 7)
Parameter
Index
(hex.)
Sub-
index
(hex.)
Data
type
Access
Min.
value
Max. value Default Explanation
Number of teach cycles
2103
1
t08U
RO
10
Depending on the environ
-
mental conditions or applica
-
tion, the light curtain may
have completed multiple
cycles after the triggering of a
teach.
Type of storage for teach values
2103
2
t08U
RW
0
1
0
0: Non-volatile storage of
teach values
1: Teach values stored only
while voltage is ON
Sensitivity adjustment for teach event
2103
3
t08U
RW
0
Sensitivity of the measure
-
ment system:
0: High function reserve (for
stable operation)
1: Medium function reserve
2: Low function reserve
Teach status
2400
1
t08S
RO
0
MAX_T08U
Information about the last
teach:
00: Teach ok
01: Teach busy
80: Teach error (bit 8 = error
bit)
Up to four beam areas can be deactivated. Deactivated beams can be assigned the logical
values 0, 1 or the value of the adjacent beam. With auto blanking activated, up to four beam
areas are automatically suppressed during teaching.
Auto blanking should only be activated during commissioning of the CML 700i to suppress inter
-
fering objects. In process mode, auto blanking should be deactivated.
For details on this topic see chapter 11.4.
NOTICE
Perform teach after changing the blanking configuration!
Perform a teach after changing the blanking configuration.
A teach can be performed via the receiver control panel or via the teach command.