Commissioning and configuration
168
BCL 548
i
Leuze electronic
10.11.3 Module 54 – Segmentation according to identifier and separator
PROFINET-IO module identifier
Module-ID 1054
Submodule-ID 1
Description
This module activates the segmentation according to identifier and separator. The param-
eters specify the identifiers to be searched for, the output mode, and the parameters for the
identifier/separator algorithm.
Parameter
Parameter length
29 byte
Parameter
Description
Addr. Data type
Value range
Default
Unit
Identifier list
Identifier 1
The identifier string is used for the identifier
list and the filtering according to the segmen-
tation.
0
STRING
5 characters null
terminated
1 … 5 bytes of
ASCII characters
‘*‘
-
Identifier 2
See identifier 1.
5
STRING
5 characters null
terminated
1 … 5 bytes of
ASCII characters
\0
-
Identifier 3
See identifier 1.
10
STRING
5 characters null
terminated
1 … 5 bytes of
ASCII characters
\0
-
Identifier 4
See identifier 1.
15
STRING
5 characters null
terminated
1 … 5 bytes of
ASCII characters
\0
-
Identifier 5
See identifier 1.
20
STRING
5 characters null
terminated
1 … 5 bytes of
ASCII characters
\0
-
Identifier output
Output with iden-
tifier
If this switch is not set, the output of the iden-
tifiers is suppressed. In this case, only the
data values belonging to the identifiers are
displayed.
25.0
Bit
0: Output of the
identifiers is
suppressed.
1: Identifiers are
output.
1
-
Output delimiter
This delimiter, if not equal to 0, is inserted
between the identifier and the associated data
value in the output.
26
UNSIGNED8
0 … 127
0
-
Segmentation acc. to identifier and separator
Identifier length
Fixed length of all identifiers in the segmen-
tation process. After this length, the text of the
identifier ends and the associated data value
starts. The end of the data value is determined
by the separator.
27
UNSIGNED8
0 … 255
0
-
Delimiter in the
identifier/sepa-
rator algorithm
The separator terminates the data value that
follows its identifier directly after the identifier
length. After the separator, the next identifier
starts.
28
UNSIGNED8
0 … 127
0
-
Table 10.33:
Parameters for module 54