Display and control panel
Leuze electronic
BCL 504
i
83
TNT 35/7-24V
Notice!
The rear cover
of this manual includes a
fold-out page
with the complete
menu structure
.
It describes the menu items in brief.
A detailed description of the individual parameters can be found in the description of the
PROFIBUS GSD modules (see chapter 10.5 "Overview of the project modules").
Attention!
If parameters are changed via the display during bus operation, the BCL 504
i
is separated
from the PROFIBUS at the moment parameter enabling is activated via the display. Param-
eters set by the PROFIBUS are moved to the background, and changes to parameters can
be made via the display. When parameter enabling is exited, the BCL 504
i
is automatically
reconnected to the PROFIBUS. Upon connection to the PROFIBUS, the BCL 504
i
receives
all parameters from the PROFIBUS master.
Changes made via the display are overwritten!
Device settings for operating the BCL 504
i
on the PROFIBUS are managed and con-
figured exclusively by the PROFIBUS master.
8.3.2
Parameter menu
Parameter handling
The
Parameter handling
submenu is used to lock and release the parameter input via the
display and for resetting to default values.
Table 8.1:
Parameter handling submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Parameter
enabling
OFF/ON
The standard setting (OFF) prevents unintended parameter
changes.
If parameter enabling is activated (ON), parameters can be
changed manually.
As long as parameter enabling is activated, the BCL 504
i
is
disconnected from the PROFIBUS.
OFF
Parameters to
default
By pressing the enter button
after selecting
Parameters to default, all parameters are reset to their
standard settings without any further security prompts.
In this case, English is selected as the display language.