Display and control panel AMS 355i
52
AMS 355
i
Leuze electronic GmbH + Co. KG
According to the criteria specified by Rockwell Automation, Configuration Recovery auto
-
matically downloads parameters to the AMS 355
i
. This results in parameters that were man
-
ually changed via the display being restored by the control to the configured AMS 355
i
data
from the EDS file. The parameters that were manually changed via the display are, thus, no
longer valid.
The address setting made on the AMS 355
i
for DeviceNet (MAC ID) is not affected by auto
-
matic changes.
Attention!
If the
Configuration Recovery
function is not activated, parameters set manually via the dis
-
play are activated the moment parameter enabling is again deactivated on the AMS 355
i
.
Note!
If a password was stored, parameter enable is not possible until this password is entered;
see "Password for parameter enable" below.
Password for parameter enable
Parameter entry on the AMS 355
i
can be protected with a password. With the AMS 355
i
, the
password is defined via the EDS file (class 100, instance 1). Therefore, the password cannot
be changed by means of display entry.
To activate parameter enable via the display (e.g. for changing an address), the password
defined in the EDS file must be entered. If parameter enable has been activated after
successfully entering the password, parameters can be temporarily changed via the display.
After parameter enable is deactivated, all changes made on the display are overwritten by
the ESD file (see above). If a new password has been assigned, this, too, is overwritten by
the password defined in the EDS file.
Note!
The
master password 2301
can enable the
AMS 355
i
at any time.