GeneRal emc - HaRmonIcs - maIns InteRFeRence
4.6 - Electromagnetic compatibility (EMC)
CAUTION:
Conformity of the drive is only assured when the mechanical and electrical installation instructions described in this
manual are adhered to.
Immunity
Standard
Description
Application
Conformity
Iec 61000-4-2
electrostatic discharges
Product casing
level 3 (industrial)
en 61000-4-2
Iec 61000-4-3 Immunity standards for radiated
radio-frequency
Product casing
level 3 (industrial)
en 61000-4-3
Iec 61000-4-4
Bursts of fast transients
control cable
level 4 (industrially hardened)
en 61000-4-4
Power cable
level 3 (industrial)
Iec 61000-4-5
shock waves
Power cables
level 4
en 61000-4-5
Iec 61000-4-6 Generic immunity standards for
conducted radio-frequency
control and power
cables
level 3 (industrial)
en 61000-4-6
en 50082-2
Generic immunity standards for
the industrial environment
-
conforming
Iec 61000-6-2
en 61000-6-2
en 61800-3
Variable speed drive standards
Conforming to the first and second environment
Iec 61800-3
en 61000-3
Emission
Standard
Description
Category
Conformity conditions
Standard(2)
With external RFI filter(1) (2)
en 61800-3
Variable speed drive standards
c1
-
-
c2
-
conforming
- cable length < 20 m
- switching frequency < 4 kHz
c3
conforming
- cable length < 100 m
- switching frequency < 4 kHz
conforming
- cable length < 100 m
- switching frequency < 6 kHz
(1) see §5.4
(2) PoWeRdRIVe md2cs
and CEM filter mounted on a metallic plate. Shielded motor cables, fixed with clamp on the metallic
plate.