28
Digidrive SK Getting Started Guide
www.leroy-somer.com
Issue Number: d
6.2
Parameter descriptions - Level 2
diS
: Mechanical brake software disabled
rEL
: Mechanical brake software enabled. Brake control via relay T5 & T6. The digital
output on terminal B3 is automatically programmed as a drive healthy output.
d IO
: Mechanical brake software enabled. Brake control via digital output B3. The relay
outputs on terminals T5 and T6 are automatically programmed as a drive healthy
output.
USEr
:Mechanical brake software enabled. Brake control to be programmed by user.
The relay and digital output are not programmed. The user should programme the
brake control to either the digital output or relay. The output not programmed to
the brake control can be programmed to indicate the required signal. (See
Digidrive SK Advanced User Guide
.)
See Pr
Defines the jog speed
No
Function
Range
Defaults
Type
11
Start/Stop logic select
0 to 6
Eur: 0, USA: 4
RW
Pr 11
Terminal B4
Terminal B5
Terminal B6
Latching
0
Enable
Run Forward
Run Reverse
No
1
/Stop
Run Forward
Run Reverse
Yes
2
Enable
Run
Forward / Reverse
No
3
/Stop
Run
Forward / Reverse
Yes
4
/Stop
Run
Jog
Yes
5
User programmable Run Forward
Run Reverse
No
6
User Programmable User Programmable User Programmable
User Programmable
A change to Pr
11
is set by pressing the
MODE key on exit from parameter edit mode.
The drive must be disabled, stopped or tripped for a change to take place. If Pr
11
is
changed while the drive is running, when the
MODE key is pressed on exit from
parameter edit mode, Pr
11
will change back to its previous value.
NOTE
M
M
No
Function
Range
Defaults
Type
12
Brake controller enable
diS, rEL, d IO, USEr
diS
RW
A change to Pr
12
is set by pressing the
MODE key on exit from parameter edit mode.
The drive must be disabled, stopped or tripped for a change to take place. If Pr
12
is
changed while the drive is running, when the
MODE key is pressed on exit from
parameter edit mode, Pr
12
will change back to its previous value.
NOTE
M
M
Great care should be taken when implementing a brake control set-up, as this may cause
a safety issue depending on the application, e.g. crane. If in doubt, contact the supplier
of the drive for further information.
WARNING
No
Function
Range
Defaults
Type
13
Not used
14
No
Function
Range
Defaults
Type
15
Jog reference
0 to 400.0 Hz
1.5
RW