IMS94S-mv1
42
7.3.2 Fault Reset
Fault reset is accomplished by disabling or re-enabling drive depending on settings
performed during drive set-up.
TABLE 10
FAULT CODES
Fault
Code Fault
Display
Code
Description
1
Overvoltage
F_OU
Drive bus voltage reached maximum level due
to regen.
2
Feedback error
F_FB
One or more motor hall sensor is inoperable or
not connected or resolver signal lost
3
Overcurrent
F_OC
Drive exceeded peak current limit.
4
Overtemperature
F_Ot
Maximum Heatsink temperature has been
reached (90-100 degree C)
5
External fault input
activated
F_EF
Digital input was programmed as external fault
input and has been activated.
6
Overspeed
F_OS
Motor reached velocity above its specified limit
7
Position error excess
F_PE
Position error exceed maximum value.
8
Bad motor data
F_bd
Motor profile data invalid or no motor was
selected for operation
9
Motor overtemperature
F_09
Motor temperature sensor (PTC) indicates motor
reached maximum temperature
10
10EN954 option fault
F_10
EN954 switch open