IMS94S-mv1
l
33
6.3.4 Peak current limit
Peak current sets Motor RMS phase current that is allowed for up to 2 Seconds.
After this two second limit, the current limit will be reduced to the value set in the
Current Limit parameter. When the motor current drops below nominal current for
two seconds, the drive will automatically enable the peak current level again. This
technique allows for high peak torque on demanding fast moves and fast start/stop
operations with high regulation bandwidth.
6.3.5 Analog input scale (Current scale)
This parameter sets analog input sensitivity for current reference used when drive
operates in Torque mode. Units for this parameter are A/Volt. To calculate value use
following formula:
Iscale = Imax / Vin max
Imax
maximum desired output current in A, (motor phase current RMS)
Vin max
max voltage fed to analog input at Imax
Example:
Imax = 5A (phase RMS)
Vin max = 10V
Iscale = Imax / Vin max = 5A / 10V = 0.5 A / Volt -> value to enter.
6.3.6 Analog input scale (Velocity scale)
This parameter sets analog input sensitivity for velocity reference used when drive
operates in Velocity mode. Units for this parameter are RPM/Volt. To calculate value
use following formula:
Vscale = VelocityMax / Vin max
Velocitymax maximum desired velocity in RPM
Vin max
max voltage fed to analog input at Velocitymax
Example:
Velocitymax = 2000 RPM
Vin max = 10V
Vscale = Velocitymax / Vin max
= 2000 / 10V
= 200 RPM / Volt (
value to enter
)
6.3.7 ACCEL/DECEL Limits (Velocity mode only)
The ACCEL setting determines the time the motor takes to ramp to a higher speed.
The DECEL setting determines the time the motor takes to ramp to a lower speed. If
the ENABLE ACCEL\DECEL LIMITS is set to DISABLE, the drive will automatically
accelerate and decelerate at maximum acceleration limited only by current limit
established by the PEAK CURRENT LIMIT and CURRENT LIMIT settings.
6.3.8 Reference (Velocity mode only)
The REFERENCE setting selects the reference signal being used.
Select Internal only when you using drive’s built-in digital signal generator (Run
Panel) for tuning purposes. Select External for normal operations.
6.3.9 Step input type
This parameter set the type of input for position reference drive expects to see. Signal
can be step and direction (S/D) type or quadrature pulse-train (Master Encoder). Refer
to 5.2.1 for details on these inputs.
Summary of Contents for SimpleServo 94
Page 1: ...MODEL 94 USERS MANUAL IMS94S mv1 ...
Page 12: ...l IMS94S mv1 10 3 2 Clearance for Cooling Air Circulation ...
Page 56: ...l IMS94S mv1 54 ...
Page 57: ...IMS94S mv1 l 55 ...
Page 58: ...l IMS94S mv1 56 ...
Page 59: ...IMS94S mv1 l 57 ...
Page 60: ...l IMS94S mv1 58 ...
Page 61: ...IMS94S mv1 l 59 ...
Page 62: ...l IMS94S mv1 60 ...
Page 63: ...IMS94S mv1 l 61 ...
Page 64: ...l IMS94S mv1 62 ...
Page 65: ...IMS94S mv1 l 63 ...