14
Parameter reference
14.1
Parameters of the standard device that are relevant to communication
92
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00637
C01501
C01502
Parameter | Name:
C00637 | Resp. to new module in MXI2
Data type: UNSIGNED_32
Index: 23939 = 0x5D83
Response if a new module has been plugged into module slot 2 of the standard device.
Selection list
(Lenze setting printed in bold)
1 Fault
6 Information
5 Warning
4 Warning Locked
3 Quick stop by trouble
0 No response
Read access
Write access
CINH
PLC-STOP
No transfer
Parameter | Name:
C01501 | Resp. to comm. error with MXI1
Data type: UNSIGNED_32
Index: 23074 = 0x5A22
Response to a communication error between an "intelligent" module in slot 1 and the standard device
Selection list
(Lenze setting printed in bold)
0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
5 Warning
Read access
Write access
CINH
PLC-STOP
No transfer
Parameter | Name:
C01502 | Resp. to comm. error with MXI2
Data type: UNSIGNED_32
Index: 23074 = 0x5A22
Response to a communication error between an "intelligent" module in slot 2 and the standard device
Selection list
(Lenze setting printed in bold)
0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
5 Warning
Read access
Write access
CINH
PLC-STOP
No transfer