Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
91
14
Parameter reference
14.1
Parameters of the standard device that are relevant to communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14
Parameter reference
This chapter supplements the parameter list and the table of attributes contained in the reference
manual and in the »Engineer« online help for the Servo Drive 9400 with the parameters of the
E94AYCER (PROFINET) communication module.
14.1
Parameters of the standard device that are relevant to communication
In this chapter communication-relevant parameters of the Servo Drive 9400 are listed in
numerically ascending order.
C00615
C00636
Reference manual/»Engineer« online help for the Servo Drive 9400
Here you will find general information on parameters.
Parameter | Name:
C00615 | Resp. to imp. device conf.
Data type: UNSIGNED_32
Index: 23960 = 0x5D98
Response to impermissible device configuration
Selection list
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
0 No response
Subcodes
Lenze setting
Info
C00615/1
0: No Response
Reserved
C00615/2
1: No Response
Resp. to imp. module in MXI1
C00615/3
1: No Response
Resp. to imp. module in MXI2
C00615/4
0: No Response
Reserved
C00615/5
0: No Response
Reserved
Read access
Write access
CINH
PLC-STOP
No transfer
Parameter | Name:
C00636 | Resp. to new module in MXI1
Data type: UNSIGNED_32
Index: 23939 = 0x5D83
Response for the case where a new module has been plugged into slot 1 of the standard device.
Selection list
(Lenze setting printed in bold)
1 Fault
6 Information
5 Warning
4 Warning Locked
3 Quick stop by trouble
0 No response
Read access
Write access
CINH
PLC-STOP
No transfer