Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018
59
Parameter reference
Parameters relevant for POWERLINK communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13910
C13915
C13920
Parameter | Name:
C13910 | Last Module Error
Data type: UNSIGNED_32
Index: 10665
d
= 29A9
h
Display of the error code of the error last occurred in the Communication Unit
Selection list
(Lenze setting printed in bold)
0 No error
297566817 Warning locked INVALID_ADDR
29122816 Software error
96239921 Fault OPER_LOST
230457649 Quick stop OPER_LOST
297566513 Warning locked OPER_LOST
431784241 Information OPER_LOST
96240229 Fault CN_SoC_LOSS
230457957 Quick stop CN_SoC_LOSS
297566821 Warning locked CN_SoC_LOSS
431784549 Information CN_SoC_LOSS
96240230 Fault COM_CRC
230457958 Quick stop COM_CRC
297566822 Warning locked COM_CRC
431784550 Information COM_CRC
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13915 | CustomerObject[16]
Data type: OCTET_STRING
Index: 10660
d
= 29A4
h
The code contains an octet string[16] for customised use.
Setting range
(min. value | unit | max. value)
Subcodes
Lenze setting
Info
C13915/1
00000000000000000000000000000
000
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13920 | Current address switch
Data type: UNSIGNED_8
Index: 10655
d
= 299F
h
The code displays the current DIP switch position (node ID).
Not all switch positions are useful. The values for node IDs assigned by means of switches are between 1 and 239.
Node address (node ID) setting (
Display range
(min. value | unit | max. value)
0
255
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT