10
Parameter reference
10.2
Parameters of the communication module for slot MXI1
74
Lenze · E94AYCEC Communication module (POWERLINK CN) · Communication Manual · DMS 3.0 EN · 08/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13075
C13078
C13079
Parameter | Name:
C13075 | EPL SDO channel width
Data type: UNSIGNED_16
Index: 11500 = 0x2CEC
EPL index: 0x1F98.0x08
The code defines the maximum user data size of asynchronous frames. Protocol-specific headers for POWERLINK,
UDP/IP and others as well as service-specific headers are to be interpreted as part of the user data.
In the configured state, the C13075 values of all EPL nodes must be identical.
Setting range
(min. value | unit | max. value)
Lenze setting
282
Byte
1500
282 bytes
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13078 | EPL CN: Max. time - MN detection
Data type: UNSIGNED_32
Index: 11497 = 0x2CE9
EPL index: 0x1F99
The code defines the time interval needed for detecting a managing node. If a booting controlled node detects a
managing node during the interval, it changes to NMT_CS_PREOPERATIONAL_1. If not, it changes to "Basic Ethernet
Mode".
Setting range
(min. value | unit | max. value)
Lenze setting
0
μ
s
4294967295
10000000
μ
s
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13079 | EPL multi-stage node declaration CN
Data type: UNSIGNED_8
Index: 11496 = 0x2CE8
EPL index: See subcodes
This code indicates in which multiplexed cycle the controlled node is queried. The value entered must not exceed
the value in code
.
If, for instance, the value "3" is entered in code
, the multiplexed cycle is repeated every three cycles. If now
the value "3" is entered for one node in C13079/x, it is always queried only in the second cycle of the three
multiplexed cycles.
Setting range
(min. value | unit | max. value)
0
Cycles
255
Subcodes
Lenze setting
Info
EPL index
C13079/1
0 cycles
0x1F9B.0x01
...
...
...
C13079/100
0 cycles
0x1F9B.0x64
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT