Commissioning
Before switching on
6
l
31
EDSMF2181IB EN 3.0
6
Commissioning
6.1
Before switching on
(
Stop!
Prior to switching on the mains voltage, check the wiring for completeness,
short−circuit and earth fault.
Automatic address assignment and automatic detection of the baud rate
The device is equipped with the following functions:
ƒ
Automatic address assignment
ƒ
Automatic detection of the baud rate
Both functions are used to prevent malfunctions in operation due to incorrectly set user
addresses and baud rate.
)
Note!
In default setting these functions are not activated.
Please refer to the related instructions on the codes
ƒ
C0350: "General address assignment" (
¶
ƒ
C0351: "Set baud rate" (
¶
Configuring the country−specific code
Before the 2181 communication module is connected to the telephone network, it may be
required to configure the country−specific code.
)
Note!
Observe the description for code C1208 (
¶