Diagnostics & error management
9.9
Error messages of the operating system
674
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Ck04: Neg. SW limit position [xx.0184.00008]
Ck17: direction conflict Ccw [xx.0184.00009]
Ck18: direction conflict Cw [xx.0184.00010]
Ck14: Target position outside SW limit position [xx.0184.00015]
Ck16: Time overflow manual operation [xx.0184.00064]
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
MCK: The device has detected that the position is outside
the negative software limit position (
).
• Increase permissible traversing range (change setting
of the software limit positions).
• Deactivate software limit position monitoring.
Response
(Lenze setting printed in bold)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Positioning profile is started in positioning mode 5 or 12
(absolute (Ccw) or absolute (Ccw) to TP); however, the
Cw rotating direction is defined by the profile
generation.
Start positioning with zero speed.
Response
(Lenze setting printed in bold)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Positioning profile is started in positioning mode 4 or 11
(absolute (Ccw) or absolute (Ccw) to TP); however, the
Ccw rotating direction is defined by the profile
generation.
Start positioning with zero speed.
Response
(Lenze setting printed in bold)
(
Adjustable response)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
MCK: It has been attempted to position a target outside
the software limit positions (
• Select a target within the software limit positions.
• Increase permissible traversing range (change setting
of the software limit positions).
• Deactivate software limit position monitoring.
Response
(Lenze setting printed in bold)
0: No Reaction
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
PC manual control: The connection monitoring has
tripped.
• The online connection between the PC and the
inverter has been interrupted for a longer period of
• Check communication link between PC and inverter.
• Check voltage supply/function of the inverter.
• Adjust the timeout (