Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
543
8
Basic drive functions (MCK)
8.4
Basic settings
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.4.5
Monitoring of the maximum travel distance
Continuous travel requests in the "
" operating mode (or relative positioning with feed in
the same direction) cause an overflow of the position integrators when the max. display area of the
position is reached and the reference is set. The same behaviour takes place in the "
"
and "
" operating modes. For this reason, a monitoring mode of the maximum travel
distance is implemented in the
Motion Control Kernel
.
• If the maximum travel distance (
) is exceeded:
will be carried out (Lenze setting: "TroubleQuickStop").
• The "
Ck07: Travel range limit exceeded
" error message is entered into the logbook.
• The internal status "reference known" is reset (the inverter is no longer referenced).
• A setting of
= "0: No Reaction" deactivates the monitoring.