Parameter reference
15.2
Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00993
C00994
C00995
C00996
Parameter | Name:
C00993 | Flying restart fct: Int. time
Data type: UNSIGNED_16
Index: 23582
d
= 5C1E
h
Time constant of the angular difference controller of the flying restart function
• The time constant is to amount between 60 ... 300 ms.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
ms
6000.0 power-related (see
)
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 10
Parameter | Name:
C00994 | Flying restart fct.: Current
Data type: INTEGER_16
Index: 23581
d
= 5C1D
h
Current to be injected during the flying restart process
• 100 %
≡
rated motor current (
).
• The flying restart current should amount to 10 ... 25 % of the rated motor current.
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00
25.00 %
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00995 | SLPSM: Controlled current setpoint
Data type: UNSIGNED_16
Index: 23580
d
= 5C1C
h
From version 10.00.00
Sensorless control for synchronous motors (SLPSM)
Setting range
(min. value | unit | max. value)
5.00
%
400.00
Subcodes
Lenze setting
Info
C00995/1
100.00 %
: Controlled accelerating current
C00995/2
20.00 %
: Controlled standstill current
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00996 | SLPSM: Switching speed
Data type: INTEGER_16
Index: 23579
d
= 5C1B
h
From version 10.00.00
Sensorless control for synchronous motors (SLPSM)
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Info
C00996/1
13.00 %
: Switching speed, closed-loop control
C00996/2
8.00 %
: Switching speed, open-loop control
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100