Fig. 71: Safety function STO
Functional sequence and error response have no adjustable parameters.
Via a safe input, if the corresponding parameter is assigned to the safe input.
Activation of the function
A data telegram is sent to the inverter via the safety bus. See chapter "
In response to the error stop request.
In response to the emergency stop request.
Parameter
Address
Name / setting range / [default setting]
Info
0x2890
STO: Source SD-In
•
Read only
0 Deactivated
1 SD-In1
2 SD-In2
3 SD-In3
4 SD-In4
0x2891
STO: Source S-Bus
•
Read only
0 Deactivated
1 Activated
0x2892:001
STO: STO: Restart
•
Read only
0 Acknowledged Restart
1 Automatic Restart
0x2893
STO active: Output
•
Read only
0 Deactivated
1 SD-Out1 positive logic
2 SD-Out1 negative logic
Safety functions
Safe Torque Off (STO)
399