7
Technical data
Operating instructions I510-Cabinet
3 Technical data
3.1
Standards and operating conditions
Conformities
CE
2014/35/EU, 2014/30/EU
EAC
TR TC 004/2011, TP TC 020/2011
RoHS 2
2011/65/EU
Approvals
C
UL
US
UL 61800-5-1, CSA 22.2 No. 274
Energy efficiency
Class IE2
EN 50598-2
Protection type
IP20
EN 60529 (except in wire range of terminals)
NEMA 250 (type 1 protection against accidental
contact only)
Open type
Only in UL-approved systems
Power systems
TT, TN
Voltage against earth: max. 300 V
IT
Apply the measures described for IT systems!
Mains switching
3 x within one minute possible
Operation with earth-leakage circuit
breaker
(120-V mains and 230-V mains)
Up to 2.2 kW 30 mA, above this 300 mA
Operation with earth-leakage circuit
breaker
(400-V mains)
Up to 2.2 kW 30 mA, above this 300 mA
Cable length for EMC
Category C2
Max. 20 m (≤0.37 kW max. 15 m)
Category C3
Max. 35 m (≤0.37 kW max. 15 m)
Switching frequencies
2, 4, 8, 16 kHz, the rated output currents apply at 45
°C and switching frequencies of 2 and 4 kHz, and at 40
°C and switching frequencies of 8 and 16 kHz
Ambient temperature
55 °C (derating of 2.5 %/ °C above 45 °C)
Max. Output frequency
0 Hz ... 599 Hz
Overload capacity
(120-V mains and 230-V mains)
200 % for 3s; 150 % for 60s
Overload capacity
(400-V mains)
200 % for 3s; Heavy Duty: 150 % for 60s; Light Duty:
125 % for 60s
3.2
Connection to the IT system
NOTE
Electrical voltage
Internal components have ground potential if the IT screws are not removed.
The monitoring devices of the IT system will be triggered.
►
Before connection to an IT system be absolutely sure to remove the IT screws.