23
Commissioning
Operating instructions I510-Cabinet
7.4.4
Group 7: Additional functions
Display code
Name
Possible settings
Keypad code
Information
P700.01
Device commands:
Load default settings
Off / ready
[0]
Only status feedback
On / start
[1]
1 = reset all parameters in the RAM memory of the inverter to the default setting that is stored in the inverter firmware.
• All parameter changes made by the user are lost during this process!
• This process may take some seconds. When the device command has been executed successfully, the value 0 is shown.
• Loading parameters has a direct effect on cyclic communication: The data exchange for control is interrupted and a communication error is
generated.
P700.03
Device commands:
Save user data
Off / ready
[0]
Only status feedback
On / start
[1]
Execute device commands
In progress
[2]
Only status feedback
Action cancelled
[3]
No access
[4]
No access
(inverter disabled)
[5]