18
Commissioning
Operating Instructions i510-Cabinet
7.4 The most important parameters at a glance
This chapter contains the most important parameters and selections. You can find a detailed description in the commissioning document. http://www.Lenze.com
The parameters are divided into the following function groups:
• Pxxx.xx group 0: Favorites
• P1xx.xx group 1: Diagnostics
• P2xx.xx group 2: Basic setting
• P3xx.xx group 3: Motor control
• P4xx.xx group 4: I/O setting
• P5xx.xx group 5: Network setting
• P6xx.xx group 6: Process controller
• P7xx.xx group 7: Additional functions
• P8xx.xx group 8: Sequencer
7.4.1
Group 0: Favorites
Group 0 contains the configurable favorites that are also contained in the groups 1 to 4. In the default setting these are the most common parameters for the solution of typical applications.
Display code
Name
Possible settings/
value ranges
Keypad code
Information
P100.00
Output frequency
x.x Hz (read only)
Display of the actual output frequency.
P103.00
Current actual
x.x % (read only)
Display of the actual motor current.
P106.00
Motor voltage
x VAC (read only)
Display of the actual motor voltage.
P150.00
Error code
- (read only)
Error message.
P200.00
Control selection
Flexible I/O
[0]
This selection enables a flexible assignment of the start, stop, and rotating direction commands with digital signal sources.
Keypad
[1]
This selection enables the motor to start exclusively via the start key of the keypad. Other signal sources for starting the motor are ignored.
P201.01
F-setp.source
Keypad
[1]
The setpoint is specified locally by the keypad.
Analog input 1
[2]
The setpoint is defined as analog signal via the analog input 1.
Analog input 2
[3]
The setpoint is defined as analog signal via the analog input 2.
HTL input
[4]
The digital inputs DI3 and DI4 can be configured as HTL input to use an HTL encoder as setpoint encoder or define the setpoint as a reference
frequency ("pulse train").
Network
[5]
The setpoint is defined as process data object via the network.
Frequency preset 1 ... 15
[11] ... [25]
For the setpoint selection, “preset” values can be parameterized and selected. All frequency presets are described in detail in the commissioning
manual. Lenze Doc Finder
P203.01
Start method
Normal
[0]
After start command, the standard ramps are active.
DC braking
[1]
After start command, the "DC braking" function is active for the time set in P704.02.
Flying restart circuit
[2]
After the start command, the flying restart circuit is active.
Premagnetization
[3]
After start command, the standard ramps are active and the premagnetization of the motor is activated. This reduces the motor current and smooths
the acceleration curve during the starting process (only relevant in V/f motor control mode).
Default setting = bold print | * Default setting is device-dependent