15
Initial switch-on
Operating instructions I510-Cabinet
7 Commissioning
DANGER
Electrical voltage
Incorrect wiring can cause unexpected states during the commissioning phase.
►
Wiring must be complete and correct.
►
Check the wiring to ensure that it is free of short circuits and earth faults.
►
Adapt the motor circuit configuration (star/delta) to the inverter.
►
Connect the motor in the correct phase relation (rotating direction).
►
Check the “Emergency off” function of the overall system.
►
Clear the hazard area.
►
Observe safety instructions and safety clearances.
7.1 Keypad module
►
Plug the keypad onto the inverter.
The keypad can also be connected and removed during operation.
6
Initial switch-on
DANGER
Electrical voltage
Incorrect wiring can cause unexpected states during the commissioning phase.
►
Wiring must be complete and correct.
►
Check the wiring to ensure that it is free of short circuits and earth faults.
►
Adapt the motor circuit configuration (star/delta) to the inverter.
►
Connect the motor in the correct phase relation (rotating direction).
►
Check the “Emergency off” function of the overall system.
►
Clear the hazard area.
►
Observe safety instructions and safety clearances.
Conditions
• The power connections must be wired.
• The digital inputs X3/DI1 (start/stop), X3/DI3 (reversal of rotation direction) and
X3/DI4 (frequency preset 20 Hz) must be wired.
• The analog input X3/AI1 must not be wired or connected to GND.
Switch on mains voltage
►
Switch on mains voltage and check readiness for operation.
Observe LED status displays “RDY” and “ERR” on the inverter front panel.
See “LED status”.
27