
13
Electrical installation
Operating instructions I510-Cabinet
5.7
Three-phase mains connection 400 V
Terminal data, 3-phase 400 V
I51AExxxF
I51BExxxF
I51AExxxF
I51AExxxF
I51AExxxF
I51AExxxF
I51AxxxF
I51AxxxF
I51AxxxF
Inverter
[kW]
0.37 ... 2.2
3 ... 4
3 ... 5.5
7.5 ... 11
0.37 ... 5.5
7.5 ... 11
0.37 ... 2.2
3 ... 5.5
7.5 ... 11
Connection
Mains connection X100
PE connection
Motor connection X105
Connection type
Pluggable
screw terminal
Pluggable
screw terminal
Screw terminal
PE screw
Pluggable
screw terminal
Screw terminal
Min. cable cross-section
mm²
1
1.5
1
Max. cable cross-section
mm²
2.5
2.5
6
16
6
16
2.5
6
16
Stripping length
mm
8
8
9
11
10
11
8
9
11
Tightening torque
Nm
0.5
0.5
0.5
1.2
2
3.4
0.5
0.5
1.2
Tools required
0.5 x 3.0
0.5 x 3.0
0.6 x 3.5
0.8 x 4.0
Torx 20
PZ2
0.5 x 3.0
0.6 x 3.5
0.8 x 4.0
Fusing data/performance data
Inverter
[kW]
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
Rated output current
(heavy duty)
A
1.3
1.8
2.4
3.2
3.9
5.6
7.3
9.5
13
16.5
23.3
-
Max. Output current (15 s)
A
2.6
3.6
4.8
6.4
7.8
11.2
14.6
19
26
33
47
-
Rated output current
(light duty)
A
-
-
-
-
-
-
-
8.8
11.9
15.6
23
28.2
Max. Output current (15 s)
A
14.6
19
26
33
47
Operation without mains choke
Fuse
Characteristic
gG/gL or gRL
-
Max. rated current
A
10
10
10
16
16
16
25
25
25
32
32
-
Circuit breaker
Characteristic
B
-
Max. rated current
A
10
10
10
16
16
16
25
25
25
32
32
-
Operation with mains choke
Fuse
Characteristic
gG/gL or gRL
Max. rated current
A
10
10
10
16
16
16
25
25
25
32
32
32
Circuit breaker
Characteristic
B
Max. rated current
A
10
10
10
16
16
16
25
25
25
32
32
32
Earth-leakage circuit breaker
3-phase mains connection
≥ 30 mA, type B
≥ 300 mA, type B
A mains choke must be used for light duty loads over 15 kW.
Mains connection
Valid for I51AExxxF inverter.
+UG
3/PE
AC 340 V ... 528 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2
L3
PE
N
L3
L2
3/N/PE
AC 400 V
-UG
Motor connection
X105 U
V
W
Rb1
Rb2
M
3~