9300 Servo PLC
System blocks
2.10
DIGITAL_IO
2-37
L
ServoPLC EN 2.0
2.10.2
Outputs_DIGITAL
Digital outputs (module number 1)
This SB conditions the digital signals, and outputs them at terminals X5/A1 ... X5/A4.
X5
Outputs_DIGITAL
1
0
C0118/1...4
A3
A1
A4
A2
1
DIGOUT_bOut1_b
DIGOUT_bOut4_b
DIGOUT_bOut3_b
DIGOUT_bOut2_b
C0444/1...4
Fig. 2-21
Outputs_DIGITAL
VariableName
DataType
SignalType
Address
DIS
DIS format
Note
DIGOUT_bOut1_b
%QX1.0.0
C0444/1
DIGOUT_bOut2_b
Bool
binary
%QX1.0.1
C0444/2
bin
DIGOUT_bOut3_b
Bool
binary
%QX1.0.2
C0444/3
bin
DIGOUT_bOut4_b
%QX1.0.3
C0444/4
Electrical data of the output terminals
Terminal
Use
Data
X5/A1
LOW level:
HIGH l
l
0 ... +4 V
13
30 V
X5/A2
Freely assignable
HIGH level:
Output current:
+13 ... +30 V
max 50 mA per output
X5/A3
Freely assignable
Output current:
max. 50 mA per output
(external resistance
≥
480
Ω
at 24 V)
X5/A4
Delay times:
(external resistance
≥
480
Ω
at 24 V)
100
µ
s ... 300
µ
s
X5/39
Ground (GND) of digital inputs and outputs
•
The terminal polarity for the outputs A1 ... A4 can be configured under C0118.
Code
LCD
Possible settings
Info
o
Lenze
Selection
o
C0118 DIGOUT pol
Terminal polarity
0
HIGH active
1
LOW active
1
0
X5/A1
2
0
X5/A2
3
0
X5/A3
4
0
X5/A4