Electrical installation
Connection data
l
36
EDKZS3YA200 DE/EN/FR/ES/IT 3.0
{
Danger!
Hazardous electrical voltage
The leakage current of the connected controllers to PE can amount
to > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe personal injury if the device is touched in the
event of an error.
Protective measures:
ƒ
Implement the measures required in the EN 61800−5−1,
particularly
– Fixed installation
– Provide a standard PE connection (PE conductor diameter
³
10 mm
2
or connect PE conductor twice)
6.2
Connection data
Sinusoidal filter
Terminal
PE screw
Connection
cross−sections
Tightening torque
Æ
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb−in]
[Nm]
[lb−in]
EZS3−115A200
35 ... 95
4/0 ... 2
6
53.1
M8
18
159.3
EZS3−150A200