Lenze · E84AYCET communication module (EtherCAT) · Communication Manual · DMS 5.0 EN · 05/2013 · TD17
95
12
Error messages
12.2
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Operational status quit [0x01bc8131]
Sync telegram failure [0x01bc8700]
Response
(Lenze setting printed in bold)
(
;
Adjustable response)
:
None
System fault
;
Fault
Trouble
;
Quick stop by trouble
;
Warning locked
Warning
;
Information
Cause
Remedy
The EtherCAT data exchange was stopped in the
"Operational" state.
See also chapter "
• Check cables and terminals.
• The master has to reset the node to the "Operational"
status. (If required, check a pending emergency
message first).
Response
(Lenze setting printed in bold)
(
;
Adjustable response)
:
None
System fault
;
Fault
Trouble
;
Quick stop by trouble
;
Warning locked
Warning
;
Information
Cause
Remedy
• The cycle time settings are faulty.
• The task time setting of a linked PLC program is faulty.
• EtherCAT master / DC master settings are incorrect.
• The sync source setting is faulty.
• Check the cycle times.
• Check the task time of a linked PLC program.
• Check the EtherCAT master / DC master settings.
of the standard device
(selection of the sync source).