Monitoring functions
Configuring monitoring functions
Current load of controller (I x t monitoring: OC5, OC7)
207
EDBCSXS064 EN 4.0
9.3.9
Current load of controller (I x t monitoring: OC5, OC7)
Fault message
Monitoring function
System variable
Possible response
TRIP
Messag
e
Warnin
g
Off
015
OC5
I x t overload
MCTRL_bIxtOverload_b
·
·
Default setting
ü
Setting possible
The I x t monitoring function monitors the current load of the axis module. The monitoring
function is set so that operation
ƒ
is permanently possible with a device output current = I
r
.
ƒ
is possible for
££
30 s with a device output current
££
1.5 x I
r
.
The overload protection of the axis module can be set with thresholds:
ƒ
adjustable threshold (OC7) via C0123
ƒ
fixed threshold (OC5) = 100 %
After an overcurrent phase, you can calculate with a recovery phase of 120 s. For a more
precise consideration, see the overcurrent characteristic and the value 3 x
t
axis module
(
The response to exceeding the adjustable threshold can be defined under C0604.
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0123 OC7 limit
90
Threshold for I x t warning (axis
module)
0
{1 %}
100 C0064 > C0123
ð
fault message
OC7 (C0604)
C0604 MONIT OC7
2
Fault response − monitoring of
Ixt device utilisation.
Ixt threshold can be set under
C0123.
0
TRIP
2
Warning
3
Off