Monitoring functions
Configuring monitoring functions
Monitoring times for process data input objects
199
EDBCSXS064 EN 4.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C2457
Monitoring time for
CANaux1...3_IN (CAN bus
interface X14)
1 CE monit time
3000
1
{1 ms}
65000 CE11 monitoring time
2 CE monit time
3000
CE12 monitoring time
3 CE monit time
3000
CE13 monitoring time
The following responses can be set for communication errors:
ƒ
0 = Error (TRIP) − controller sets controller inhibit (CINH)
ƒ
2 = Warning
ƒ
3 = Monitoring is switched off
Codes for setting the response to the monitoring functions:
CAN bus interface
Code
Monitoring
X4
ECSxS/P/M: MotionBus (CAN)
ECSxA: System bus (CAN)
C0591
CAN1_IN ("CE1")
C0592
CAN2_IN ("CE2")
C0593
CAN3_IN ("CE3")
C0595
Bus off ("CE4")
C0603
Gateway function ("CE5")
X14
System bus (CAN)
C2481
CANaux1_IN ("CE11")
C2482
CANaux2_IN ("CE12")
C2483
CANaux3_IN ("CE13")
C2484
Bus off ("CE14")
C2485
Gateway function ("CE15")
The input signals (CAN1...3_IN/CANaux1...3_IN) can also be used as binary output signals,
e.g. for the assignment of the output terminal.
Bus off
If the controller disconnects from the CAN bus due to faulty telegrams, the signal
"BusOffState" (CE4/CE14) is set.
"BusOffState" can activate an error (TRIP) or warning. The signal can also be switched off.
The response is set under C0595/C2484. You can also assign the terminal output for this.