Commissioning
Selecting the operating mode/control structure
126
EDBCSXS064 EN 4.0
6.10
Selecting the operating mode/control structure
For frequent applications, the controller−internal signal processing is saved in basic
configurations hich can be selected via C3005:
ƒ
Speed control:
Code
Value
Interfaces
Application
examples
Functional
description
C3005
1000
Activation/setpoint via analog input
1003
Control / setpoint via AIF
1005
Control / setpoint via MotionBus (CAN)
ƒ
Torque control:
Code
Value
Interfaces
Application
examples
Functional
description
C3005
4000
Activation/setpoint via analog input
4003
Control / setpoint via AIF
4005
Control / setpoint via MotionBus (CAN)
Stop!
When the internal control structure is changed, another terminal assignment
may result!
In the GDC the code C3005 can be found in the parameter menu under
ƒ
Short setup
Speed
(for speed control).
ƒ
Short setup
Torque
(for torque control).
ECSXA305
Fig. 6−8
GDC view: short setup of the speed control ("Speed")