Electrical installation
Cable specification
EDK94AYCIB DE/EN/FR/ES/IT 2.0
47
H2 Kabelspezifikation−busltgslaenge
Cable specification
General characteristics
Cable type
Sold by the meter,
(e.g. PHOENIX CONTACT: IBS RBC Meter−T, Order No.
28 06 28 6)
Number of conductors
3 × 2, twisted pairs, with shared shield
Conductor cross−section
> 0.2 mm
2
DC cable resistance
< 96
W
/km
Impedance (characteristic)
l
120
W
±
20 % (f = 64 kHz)
l
100
W
±
15
W
(f > 1 MHz)
Capacitance per unit length
< 60 nF/km (f = 800 Hz)
Bus cable length
Adapt the baud rate to the length of the bus cable:
Baud rate
Length of cable between the individual INTERBUS nodes
500 kBit/s
400 m
2 Mbits/s
150 m
Note!
Select a baud rate that matches the data volume, cycle time and number of
nodes and that is as high as is necessary for the application.