4.4
Protective insulation
Danger!
Dangerous electrical voltage
If Servo Drives 9400 are used on a corner grounded system with a rated mains
voltage
≥
400 V, external measures need to be implemented to provide reliable
protection against accidental contact.
Possible consequences:
• Death or serious injury
Protective measures:
• If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
– there must be a double isolating distance.
– the components to be connected must be provided with a second isolating
distance.
Note!
The available protective insulation in Servo Drives 9400 is implemented in
accordance with EN 61800-5-1.