E94AYCCA communication manual (CANopen®)
Implemented CANopen objects
156
L
EDS94AYCCA EN 5.0 - 06/2012
I-1003 - Pre-defined error field
Error history
This object indicates that an error has occurred in the communication module and in the
standard device.
Index:
I-1003
Name:
Pre-defined error field
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Number of errors
0
0
255 rw
U8
1 ... 10: Standard error field
-
0
4294967295 ro
U32
Subindex
Meaning
0
Number of the error messages stored
1 ... 10
Display of the error list
The error messages (U32) consist of a 16-bit error code and a 16-bit manufacturer-
specific information field.
Note!
The values in the "standard error field" under subindexes 1 ... 10 will be deleted
if the subindex "number of recorded errors" is overwritten with the value "0".
Emergency
error code
Cause
Entry in the error
register
0x0000
One of several errors eliminated
0xxx
Elimination of an individual error
(afterwards error-free state)
0x00
0x1000
Standard device is in error status (error response "Trouble",
"Message", "Warning", "Fault", "Quick stop by trouble" or "System
fault")
0x01
0x3100
Supply voltage of standard device faulty or failed
0x01
0x8100
Communication error (warning)
0x11
0x8130
Life guard error or heartbeat error
0x11
0x8150
Collision of COB-IDs: an ID parameterised for reception also is used
for transmission.
0x11
0x8210
PDO length is shorter than the expected PDO length
0x11
0x8220
PDO length is longer than the expected PDO length
0x11
0x8700
Sync telegram monitoring
0x11