Technical data
General data and operating conditions
17
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4
Technical data
4.1
General data and operating conditions
Hardware manual for Inverter Drives 8400 motec
Here you will find the
ambient conditions
and information on the
electromagnetic
compatibility (EMC)
that also apply to the Communication Unit.
Range
Values
Order designation
• E84DGFCGxNx (EtherNet/IP)
• E84DGFCGxJx (EtherNet/IP + Safety)
Communication profile
EtherNet/IP
Standards / specifications
Safety engineering: EN 954-1, EN 13849-1, IEC 61508
(up to safety category 4)
Interface for communication
• EtherNet/IP port 1: M12 socket, 5-pin, D-coded
• EtherNet/IP port 2: M12 socket, 5-pin, D-coded
Network topology
Tree, star, and line
Type of node
Adapter (slave)
Number of nodes
Max. 254 in the subnetwork
Max. cable length
100 m
Vendor ID
587 (0x24B), Lenze (’Lenze AC Tech’ in older Rockwell data)
Device type
2 (0x02), AC Drive
Product code
8440 (0x20F8)
Baud rate
• 10 Mbps
• 100 Mbps
Transmission mode
Half duplex / full duplex
Switching method
Store-and-forward / cut-through
Switch latency
Approx. 125
μ
s at max. telegram length
External voltage supply
• U = 24 V DC (20 V - 0 % ... 29 V + 0 %)
• I
max
= 400 mA
Conformities, approvals
• CE
• UR / cUR
(see also hardware manual)