Lenze · E84AYCEC communication module (POWERLINK) · EDS84AYCEC EN 4.0 - 02/2019
37
Commissioning
Node address setting
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2
Node address setting
The node address is set via the two front panel rotary coding switches "Node ID".
[6-1]
Rotary coding switches "Node ID"
• The labelling of the rotary coding switches corresponds to the values for determining the node
address.
• Valid addresses for the communication module in the EPL network:
• 1 … 100: Controlled node with Lenze module E94AYCEP as managing node
• 1 … 239: Controlled node with managing node of another manufacturer
• The corresponding Ethernet IP address of the communication module results from the address
setting of the rotary coding switches:
• IP address: 192.168.100.[
EPL address
]
Note!
• Each network node address must only be used once.
• The node address setting in the configuration software (e.g. »Engineer«) and the ro-
tary encoder switches must be identical for each node.
• Adjustable address range: 1 ... 239
• Switch the voltage supply of the communication module off and on again to activate
changed settings.
Symbol_NodeID