Montageanleitung

Mounting Instructions

Instructions de montage

EDK82ZAFSC−010

.=#w

Ä.=#wä

STANDARD−I/O PT 

   

E82ZAFSC010

Funktionsmodul

Function module

Module de fonction

   

   

   

     

     

Summary of Contents for E82ZAFSC010

Page 1: ...Montageanleitung Mounting Instructions Instructions de montage EDK82ZAFSC 010 w Ä wä STANDARD I O PT E82ZAFSC010 Funktionsmodul Function module Module de fonction ...

Page 2: ...ie enthaltenen Sicherheitshinweise Please read these instructions and the documentation of the standard device before you start working Observe the safety instructions given therein Lire le présent fascicule et la documentation relative à l appareil de base avant toute manipulation de l équipement Respecter les consignes de sécurité fournies ...

Page 3: ...FR 6 1 3 ausklappbild DUMMY_NUM_Reset E82ZAFS010A Funktionsmodul E82ZAFSC010 Schalter zur Konfigurierung des Analogeingangs Klemme X3 8 21 Digitale und analoge Ein und Ausgänge Steckerleiste X3 19 Typenschild 12 0Abb 0Tab 0 ...

Page 4: ...eibung 10 Funktion 10 Bestimmungsgemäße Verwendung 10 Lieferumfang 11 Identifikation 12 4 Technische Daten 13 Anschlussdaten 13 Einsatzbedingungen 13 Abmessungen 14 5 Mechanische Installation 15 6 Elektrische Installation 16 EMV gerechte Verdrahtung 16 Verdrahtung 17 7 Inbetriebnahme 20 Vor dem ersten Einschalten 20 Schalterstellung 21 Inbetriebnahmeschritte 22 ...

Page 5: ...ion des Funktionsmoduls ƒ Informationen zur Inbetriebnahme des Funktionsmoduls ƒ Technische Daten Informationen zur Gültigkeit Die Informationen in dieser Dokumentation sind gültig für folgende Geräte Funktionsmodul Typenbezeichnung ab Hardwarestand STANDARD I O PT E82ZAFSC010 3A Zielgruppe Diese Dokumentation wendet sich an Personen die das beschriebene Produkt nach Projekt vorgabe installieren u...

Page 6: ...mentation verwendet folgende Konventionen zur Unterscheidung verschiede ner Arten von Information Informationsart Auszeichnung Beispiele Hinweise Zahlenschreibweise Dezimaltrennzeichen Punkt Es wird generell der Dezimalpunkt verwendet Beispiel 1234 56 Symbole Seitenverweis Verweis auf eine andere Seite mit zu sätzlichen Informationen Beispiel 16 siehe Seite 16 ...

Page 7: ...gramm und Signalwort Bedeutung Gefahr Gefahr von Personenschäden durch gefährliche elektri sche Spannung Hinweis auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folge haben kann wenn nicht die entsprechenden Maßnahmen getroffen werden Gefahr Gefahr von Personenschäden durch eine allgemeine Ge fahrenquelle Hinweis auf eine unmittelbar drohende Gefahr die den Tod oder ...

Page 8: ...DK82ZAFSC 010 DE EN FR 6 1 8 H2_Def_Hinweise SIC_pikt_DE Anwendungshinweise Piktogramm und Signalwort Bedeutung Hinweis Wichtiger Hinweis für die störungsfreie Funktion Tipp Nützlicher Tipp für die einfache Handhabung Verweis auf andere Dokumentation ...

Page 9: ...ie in der Dokumentation zum Grundgerät enthaltenen Sicherheitshinweise und Restgefahren Stop Elektrostatische Entladung Durch elektrostatische Entladung können elektronische Bauteile innerhalb des Funkionsmoduls beschädigt oder zerstört werden Mögliche Folgen ƒ Das Funktionsmodul ist defekt ƒ Die Feldbus Kommunikation ist nicht möglich oder fehlerhaft Schutzmaßnahmen ƒ Befreien Sie sich vor dem Be...

Page 10: ... Antriebs SPS mit analogen und digitalen Steuersignalen Bestimmungsgemäße Verwendung Das Funktionsmodul ƒ ist eine Zubehör Baugruppe die mit folgenden Lenze Grundgeräten eingesetzt werden kann Produktreihe Gerätebezeichnung ab Hardwarestand Frequenzumrichter 8200 vector Vx14 Antriebs SPS Drive PLC 1x20 ƒ ist ein Betriebsmittel zum Einsatz in industriellen Starkstromanlagen Jede andere Verwendung g...

Page 11: ...11 H2_Lieferumf Liefumfang_E82ZAFSC010 Lieferumfang E82ZAFX007 012 E82ZAFS010A Pos Lieferumfang Ausführliche Information Funktionsmodul E82ZAFSC010 Steckerleiste mit Federkraftanschluss 13 polig 19 Befestigungsbügel siehe Dokumentation 8200 vector Montageanleitung ...

Page 12: ...tion Typenschluessel_e82zafsc010 Identifikation E82AF000P0B201XX APPLICATION 010 3A22 A22 A22 APPLICATION 010 3A22 L Type Id No Prod No Ser No E82ZAFX005 E82ZAF S C 010 3A Produktreihe STANDARD I O Gerätegeneration Variante 010 PT Plug Terminal mit Feder kraftanschluss Hardwarestand ...

Page 13: ...lemme X3 39 GND2 20 Belastbarkeit S Imax 40 mA 28 Eingangswiderstand 3 3 kW 1 HIGH 12 30 V SPS Pegel HTL 0 LOW 0 3 V SPS Pegel HTL E1 1 E2 1 E3 E4 39 potenzialgetrennt zu Klemme X3 7 GND1 A1 Belastbarkeit Imax 10 mA bei interner Versorgung Imax 50 mA bei externer Versorgung 1 Wahlweise Frequenzeingang 0 10 kHz einspurig oder 0 1 kHz zweispurig Konfig über C0425 Einsatzbedingungen Umgebungsbedingun...

Page 14: ...4 Technische Daten Abmessungen EDK82ZAFSC 010 DE EN FR 6 1 14 H2_Abmess AlleMaßeInMM Abmessungen E82ZAFS010A alle Maße in mm ...

Page 15: ...hen Installation des Funktionsmoduls den Hinweisen in der Mon tageanleitung des Grundgerätes Die Montageanleitung des Grundgerätes ƒ ist Teil des Lieferumfangs und liegt jedem Gerät bei ƒ gibt Hinweise um Beschädigungen durch unsachgemäße Behandlung zu vermeiden ƒ beschreibt die einzuhaltende Reihenfolge der Installationsschritte ...

Page 16: ...ƒ Steuerleitungen getrennt von Motorleitungen verlegen ƒ Schirme so weit wie möglich an die Klemmen führen ungeschirmte Aderlänge 40 mm ƒ Legen Sie die Schirme der Steuerleitungen bzw Datenleitungen wie folgt auf Einseitig am Umrichter bei Leitungen mit analogen Signalen Beidseitig bei Leitungen mit digitalen Signalen ƒ Beachten Sie die weiteren Hinweise zur EMV gerechten Verdrahtung in der Dokume...

Page 17: ...el ohne Aderendhülse 1 5 mm2 AWG 16 mit Aderendhülse ohne Kunststoffhülse 1 5 mm2 AWG 16 mit Aderendhülse mit Kunststoffhülse 0 5 mm2 AWG 20 Abisolierlänge 9 mm Stop Um Steckerleisten und Kontakte nicht zu beschädigen ƒ Steckerleisten nur aufstecken abziehen wenn der Antriebsregler vom Netz getrennt ist ƒ Steckerleisten erst verdrahten dann aufstecken ƒ Nicht belegte Steckerleisten ebenfalls aufst...

Page 18: ...Eingänge 62 8 9 20 28 E1 E2 E3 E4 39 A1 59 X3 GND1 GND2 5V 20V 8 9 7 0 5 V 1k 10k AIN1 AOUT1 DIGOUT1 7 E82ZAFS001 Versorgung über eine externe Spannungsquelle ƒ X3 28 Reglersperre CINH ƒ X3 E1 X3 E4 digitale Eingänge GND2 62 8 9 20 28 E1 E2 E3 E4 39 A1 59 X3 7 GND1 5V 20V _ 24 V ext 12 V DC 0 30 V DC 0 max 120 mA AIN1 AOUT1 DIGOUT1 0 5 V 1k 10k E82ZAFS002 Für den Betrieb notwendige Mindestverdraht...

Page 19: ...d Ausgänge 20 V 10 Bezug X3 7 28 Digitale Eingänge Reglersperre CINH 1 Freigabe E1 3 Aktivierung von Festfrequenzen JOG JOG1 20 Hz JOG2 30 Hz JOG3 40 Hz E1 E2 JOG1 1 0 E2 3 JOG2 0 1 JOG3 1 1 E3 Gleichstrombremse DCB 1 DCB E4 Drehrichtungsumkehr Rechts Linkslauf CW CCW E4 CW 0 CCW 1 39 GND2 Bezugspotenzial für digitale Signale A1 Digitaler Ausgang Betriebsbereit l interne Versorgung l externe Verso...

Page 20: ...ellung abweichenden Konfiguration durchführen lesen Sie die Anweisungen Individuelle Einstellungen 22 ƒ Achten Sie darauf dass Sie mit dem DIP Schalter am Funktionsmodul den Sollwertbereich richtig eingestellt haben 21 dass C0034 an die Einstellung des DIP Schalters angepasst ist 21 Beispiel Sollwertvorgabe 0 V 5 V über Potenziometer an X3 7 X3 8 und X3 9 ð C0034 0 DIP Schalter 1 2 4 und 5 OFF 3 O...

Page 21: ... falsch interpretiert wird ƒ Wird ein Sollwertpotentiometer intern über X3 9 versorgt unbedingt die DIP Schalter auf den Spannungsbereich 0 5 V einstellen Andernfalls kann nicht der ganze Drehzahlbereich durchfahren werden Signal an X3 8 Schalterstellung C0034 1 2 3 4 5 0 5 V OFF OFF ON OFF OFF 0 0 10 V Lenze Einstellung OFF OFF ON OFF ON 0 0 20 mA OFF OFF ON ON OFF 0 4 20 mA OFF OFF ON ON OFF 1 4...

Page 22: ...tslauf E1 E2 E3 E4 LOW l Linkslauf E1 E2 E3 LOW E4 HIGH Individuelle Einstellung l Digitale Eingänge über C0007 oder C0410 anpassen l Digitale Eingänge so ansteuern dass der Antrieb nach Reglerfreigabe über Klemme anlaufen kann 3 Sollwert vorgeben Lenze Einstellung Sollwert 0 10 V Individuelle Einstellung l Je nach Stellung des DIP Schalters am Funktionsmodul Leitstrom an X3 8 anlegen oder Leitspa...

Page 23: ...el an X3 28 anliegt Reglerfreigabe über Klemme ƒ Beachten Sie dass die Reglersperre über mehrere Quellen gesetzt werden kann Die Quellen wirken wie eine Reihenschaltung von Schaltern ƒ Wenn der Antrieb trotz Reglerfreigabe über X3 28 nicht anläuft überprüfen Sie ob noch über eine andere Quelle die Reglersperre gesetzt ist Eine andere Quelle könnte die Taste des Keypad sein ...

Page 24: ...7 Inbetriebnahme Inbetriebnahmeschritte EDK82ZAFSC 010 DE EN FR 6 1 24 H2_Inbetriebnahmeschritte DUMMYSEITEVOR ...

Page 25: ... 6 1 25 ausklappbild DUMMY_NUM_Reset E82ZAFS010A E82ZAFSC010function module Switch for the configuration of the analog input terminal X3 8 43 Digital and analog inputs and outputs plug connector X3 41 Nameplate 34 0Fig 0Tab 0 ...

Page 26: ...ct description 32 Function 32 Application as directed 32 Scope of supply 33 Identification 34 4 Technical data 35 Connection data 35 Operating conditions 35 Dimensions 36 5 Mechanical installation 37 6 Electrical installation 38 EMC compliant wiring 38 Wiring 39 7 Commissioning 42 Before switching on 42 Switch position 43 Commissioning steps 44 ...

Page 27: ...of the function module ƒ Information about the commissioning of the function module ƒ Technical data Validity information The information given in this documentation is valid for the following devices Function module Type designation from hardware version STANDARD I O PT E82ZAFSC010 3A Target group This documentation is intended for persons who install and commission the described product accordin...

Page 28: ...mentation uses the following conventions to distinguish between different types of information Type of information Identification Examples notes Numbers Decimal separator Point The decimal point is used throughout this documentation Example 1234 56 Symbols Page reference Reference to another page with additional information Example 16 see page 16 ...

Page 29: ...revent dangerous situations Pictograph and signal word Meaning Danger Danger of personal injury through dangerous electrical voltage Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken Danger Danger of personal injury through a general source of danger Reference to an imminent danger that may result in death or serious per...

Page 30: ...ed EDK82ZAFSC 010 DE EN FR 6 1 30 H2_Def_Hinweise SIC_pikt_EN Application notes Pictograph and signal word Meaning Note Important note to ensure troublefree operation Tip Useful tip for simple handling Reference to another documentation ...

Page 31: ... assets Observe the safety instructions and residual hazards included in the documentation of the standard device Stop Electrostatic discharge Electronic components within the function module can be damaged or destroyed by electrostatic discharge Possible consequences ƒ The function module is defective ƒ Fieldbus communication is not possible or faulty Protective measures ƒ Free yourself from any ...

Page 32: ...d the Lenze Drive PLC with analog and digital control signals Application as directed The function module ƒ is an accessory module for use in conjunction with the following Lenze standard devices Product range Product name from hardware version Frequency inverter 8200 vector Vx14 Drive PLC Drive PLC 1x20 ƒ is a device to be used in industrial power systems Any other use shall be deemed inappropria...

Page 33: ...1 33 H2_Lieferumf Liefumfang_E82ZAFSC010 Scope of supply E82ZAFX007 012 E82ZAFS010A Pos Scope of supply Detailed information E82ZAFSC010function module Plug connector with spring connection 13 pole 41 Mounting clip see documentation 8200 vector Mounting Instructions ...

Page 34: ...ikation Typenschluessel_e82zafsc010 Identification E82AF000P0B201XX APPLICATION 010 3A22 A22 A22 APPLICATION 010 3A22 L Type Id No Prod No Ser No E82ZAFX005 E82ZAF E C 010 3A Product series STANDARD I O Version Variant 010 PT plug terminal with spring connection Hardware version ...

Page 35: ...ted from terminal X3 39 GND2 20 Load capacity S Imax 40 mA 28 Input resistance 3 3 kW 1 HIGH 12 30 V PLC level HTL 0 LOW 0 3 V PLC level HTL E1 1 E2 1 E3 E4 39 isolated from terminal X3 7 GND1 A1 Load capacity Imax 10 mA with internal supply Imax 50 mA with external supply 1 Frequency input alternatively 0 10 kHz single track or 0 1 kHz two track config via C0425 Operating conditions Ambient condi...

Page 36: ...4 Technical data Dimensions EDK82ZAFSC 010 DE EN FR 6 1 36 H2_Abmess AlleMaßeInMM Dimensions E82ZAFS010A All dimensions in mm ...

Page 37: ...tructions for the standard device for the mechanical installation of the function module The Mounting Instructions for the standard device ƒ are part of the scope of supply and are enclosed with each device ƒ provide tips to avoid damage provide tips to avoid damage through improper handling ƒ describe the obligatory order of installation steps ...

Page 38: ...cables from motor cables ƒ Lead the shields as far as possible to the terminals unshielded core length 40 mm ƒ Connect control and data cable shields as follows Analog signal cable shields must be connected with one end at the inverter Digital signal cable shields must be connected with both ends ƒ More information about wiring according to EMC guidelines can be obtained from the corresponding doc...

Page 39: ... AWG 16 with wire end ferrule without plastic sleeve 1 5 mm2 AWG 16 with wire end ferrule with plastic sleeve 0 5 mm2 AWG 20 Stripping length 9 mm Stop Observe the following to prevent any damage to plug connectors and contacts ƒ Only pug in unplug the plug connectors when the controller is disconnected from the mains ƒ Wire the plug connectors before plugging them in ƒ Unused plug connectors must...

Page 40: ...al inputs 62 8 9 20 28 E1 E2 E3 E4 39 A1 59 X3 GND1 GND2 5V 20V 8 9 7 0 5 V 1k 10k AIN1 AOUT1 DIGOUT1 7 E82ZAFS001 Supply via an external voltage source ƒ X3 28 controller inhibit CINH ƒ X3 E1 X3 E4 digital inputs GND2 62 8 9 20 28 E1 E2 E3 E4 39 A1 59 X3 7 GND1 5V 20V _ 24 V ext 12 V DC 0 30 V DC 0 max 120 mA AIN1 AOUT1 DIGOUT1 0 5 V 1k 10k E82ZAFS002 The min wiring requirements for operation ...

Page 41: ...nputs and outputs 20 V 10 ref X3 7 28 Digital inputs Controller inhibit CINH 1 enable E1 3 Activation of JOG frequencies JOG1 20 Hz JOG2 30 Hz JOG3 40 Hz e1 E2 JOG1 1 0 E2 3 JOG2 0 1 JOG3 1 1 E3 DC injection brake DCB 1 DCB E4 Change of direction of rotation CW CCW rotation E4 CW 0 CCW 1 39 GND2 Reference potential for digital signals A1 Digital output Ready for operation l internal supply l exter...

Page 42: ...iguration different from the Lenze setting read the instructions on Individual Settings 44 ƒ Make sure that you have correctly set the setpoint range with the DIP switch on the function module 43 that C0034 is adjusted to the settings of the DIP switch 43 Example setpoint selection 0 V 5 V via potentiometer at X3 7 X3 8 and X3 9 ð C0034 0 DIP switch 1 2 4 and 5 OFF 3 ON ...

Page 43: ...ectly by the basic device ƒ If a setpoint potentiometer is supplied internally via X3 9 make sure to set the DIP switch to the voltage range 0 5 V Otherwise it will be impossible to cover the entire speed range Signal at X3 8 Switch position C0034 1 2 3 4 5 0 5V OFF OFF ON OFF OFF 0 0 10 V Lenze setting OFF OFF ON OFF ON 0 0 20 mA OFF OFF ON ON OFF 0 4 20 mA OFF OFF ON ON OFF 1 4 20 mA open circui...

Page 44: ... E1 E2 E3 E4 LOW l CCW rotation E1 E2 E3 LOW E4 HIGH Individual setting l Adapt digital inputs under C0007 or C0410 l The digital inputs must be controlled so that the drive can start via terminal after controller enable 3 Provide a setpoint Lenze setting Setpoint 0 10 V Individual setting l Depending on the position of the DIP switch at the function module apply master current to X3 8 or Apply ma...

Page 45: ...el is applied to X3 28 controller release via terminal ƒ Please observe that the controller can be inhibited through various sources All sources act like a series connection of switches ƒ If the drive does not start in spite of the controller release via X3 28 check if the controller inhibit is set via another source Another source could be the key of the keypad ...

Page 46: ...7 Commissioning Commissioning steps EDK82ZAFSC 010 DE EN FR 6 1 46 H2_Inbetriebnahmeschritte DUMMYSEITEVOR ...

Page 47: ...bild DUMMY_NUM_Reset E82ZAFS010A Module de fonction E82ZAFSC010 Interrupteur pour la configuration de l entrée analogique borne X3 8 65 Entrées et sorties numériques et analogiques bornier enfichable X3 63 Plaque signalétique 56 0Fig 0Tab 0 ...

Page 48: ...54 Utilisation conforme à la fonction 54 Équipement livré 55 Identification 56 4 Spécifications techniques 57 Données de raccordement 57 Conditions d utilisation 57 Encombrements 58 5 Installation mécanique 59 6 Installation électrique 60 Câblage conforme CEM 60 Câblage 61 7 Mise en service 64 Avant la première mise sous tension 64 Position de l interrupteur 65 Etapes de mise en service 66 ...

Page 49: ...tion ƒ des informations sur la mise en service du module de fonction ƒ les spécifications techniques Validité Les informations contenues dans le présent document s appliquent aux appareils suivants Module de fonction Référence de commande A partir de la version matérielle E S STANDARD PT E82ZAFSC010 3A Public visé Ce document est destiné aux personnes chargées d installer et de mettre en service l...

Page 50: ...es différents types d information cette documentation utilise les conventions suivantes Type d information Aperçu Exemples remarques Représentation des chiffres Séparateur décimal Point Le point décimal est généralement utilisé Exemple 1234 56 Pictogrammes Renvoi à une page Renvoi à une autre page présentant des informations supplémentaires Exemple 16 voir page 16 ...

Page 51: ...ation dangereuse pour les personnes en raison d une tension électrique élevée Indication d un danger imminent qui peut avoir pour conséquences des blessures mortelles ou très graves en cas de non respect des consignes de sécurité correspondantes Danger Situation dangereuse pour les personnes en raison d un danger d ordre général Indication d un danger imminent qui peut avoir pour conséquences des ...

Page 52: ...N FR 6 1 52 H2_Def_Hinweise SIC_pikt_FR Consignes d utilisation Pictogramme et mot associé Explication Remarque importante Remarque importante pour assurer un fonctionnement correct Conseil Conseil utile pour faciliter la mise en uvre Renvoi à une autre documentation ...

Page 53: ...s de sécurité et des dangers résiduels énoncés dans la documentation de l appareil de base Stop Décharges électrostatiques Les décharges électrostatiques peuvent endommager ou détruire les composants électroniques situés à l intérieur du module de fonction Risques encourus ƒ Module de fonction en panne ƒ La communication par bus de terrain est impossible ou erronée Mesures de protection ƒ Se débar...

Page 54: ...x de commande analogiques et numériques Utilisation conforme à la fonction Le module de fonction ƒ est un module additionnel qui peut être utilisé avec les appareils de base suivants Série d appareils Désignation de l appareil A partir de la version matérielle Convertisseurs de fréquence 8200 vector Vx14 API pour entraînements Drive PLC 1x20 ƒ est un moyen de production à utiliser dans des install...

Page 55: ...fang_E82ZAFSC010 Équipement livré E82ZAFX007 012 E82ZAFS010A Pos Equipement livré Informations détaillées Module de fonction E82ZAFSC010 Connecteur avec raccordement par lames de ressorts à 13 broches 63 Etrier de fixation Voir la documentation de l appareil 8200 vector Instructions de montage ...

Page 56: ...üssel E82ZAFSC010 Identification E82AF000P0B201XX APPLICATION 010 3A22 A22 A22 APPLICATION 010 3A22 L Type Id No Prod No Ser No E82ZAFX005 E82ZAF S C 010 3A Série d appareils E S STANDARD Génération d appareils Variante 010 PT Plug Terminal avec raccordement par lames de ressorts Version matérielle ...

Page 57: ... GND2 20 Charge admissible S Imax 40 mA 28 Résistance d entrée 3 3 kW 1 HAUT 12 30 V niveau de l API HTL 0 BAS 0 3 V niveau de l API HTL E1 1 E2 1 E3 E4 39 Avec séparation de potentiel sur la borne X3 7 GND1 A1 Charge admissible Imax 10 mA avec alimentation interne Imax 50 mA avec alimentation externe 1 Au choix entrée de fréquence 0 10 kHz à une voie ou 0 1 kHz à deux voies configuration via C042...

Page 58: ...4 Spécifications techniques Encombrements EDK82ZAFSC 010 DE EN FR 6 1 58 H2_Abmess AlleMaßeInMM Encombrements E82ZAFS010A Toutes les cotes en mm ...

Page 59: ...vre les consignes fournies dans les instructions de montage de l appareil de base Les instructions de montage de l appareil de base ƒ font partie de la livraison standard et sont comprises dans l emballage ƒ contiennent des consignes pour éviter des dommages dus à un emploi contre indiqué ƒ décrivent l ordre à respecter pour les opérations d installation ...

Page 60: ...nt des câbles moteur ƒ Conduire le blindage aussi loin que possible vers les bornes longueur de fil sans blindage 40 mm ƒ Pour poser les blindages des câbles de commande ou des lignes de données procédez comme suit D un seul côté du convertisseur pour les câbles avec des signaux analogiques Des deux côtés pour les câbles avec des signaux numériques ƒ Respectez les autres consignes relatives au câb...

Page 61: ...16 Souple sans embout 1 5 mm2 AWG 16 avec embout sans cosse en plastique 1 5 mm2 AWG 16 avec embout et cosse en plastique 0 5 mm2 AWG 20 Longueur du fil dénudé 9 mm Stop Pour éviter d endommager les borniers et les contacts ƒ Enficher et retirer les borniers uniquement lorsque le variateur est coupé du réseau ƒ Procéder au câblage des borniers avant de les enficher ƒ Enficher également des bornier...

Page 62: ...ériques 62 8 9 20 28 E1 E2 E3 E4 39 A1 59 X3 GND1 GND2 5V 20V 8 9 7 0 5 V 1k 10k AIN1 AOUT1 DIGOUT1 7 E82ZAFS001 Alimentation via une source de tension externe ƒ X3 28 blocage variateur CINH ƒ X3 E1 X3 E4 entrées numériques GND2 62 8 9 20 28 E1 E2 E3 E4 39 A1 59 X3 7 GND1 5V 20V _ 24 V ext 12 V DC 0 30 V DC 0 max 120 mA AIN1 AOUT1 DIGOUT1 0 5 V 1k 10k E82ZAFS002 Câblage minimal nécessaire au fonct...

Page 63: ... numériques 20 V 10 référence X3 7 28 Entrées numériques Blocage variateur CINH 1 Déblocage E1 3 Activation des fréquences fixes JOG JOG1 20 Hz JOG2 30 Hz JOG3 40 Hz E1 E2 JOG1 1 0 E2 3 JOG2 0 1 JOG3 1 1 E3 Frein CC DCB 1 DCB E4 Inversion du sens de rotation Rotation horaire antihoraire CW CCW E4 CW 0 CCW 1 39 GND2 potentiel de référence pour les signaux numériques A1 Sortie numérique Opérationnel...

Page 64: ...e configuration différente du réglage Lenze lisez les instructions Réglages individuels 66 ƒ Assurez vous que la plage de la consigne est réglée correctement à l aide de l interrupteur DIP au niveau du module de fonction 65 que C0034 est adapté au réglage de l interrupteur DIP 65 Exemple réglage de la consigne 0 V 5 V via le potentiomètre au niveau de X3 7 X3 8 et X3 9 ð C0034 0 interrupteurs DIP ...

Page 65: ...nterprété par l appareil de base ƒ Si un potentiomètre de consigne est alimenté en interne via X3 9 régler impérativement l interrupteur DIP sur la plage de tension 0 5 V Autrement la plage de vitesse ne pourra pas être parcourue en entier Signal sur X3 8 Position interrupteur C0034 1 2 3 4 5 0 5 V OFF OFF ON OFF OFF 0 0 10 V réglage Lenze OFF OFF ON OFF ON 0 0 à 20 mA OFF OFF ON ON OFF 0 4 à 20 m...

Page 66: ...horaire E1 E2 E3 LOW BAS E4 HIGH HAUT Réglage individuel l Adapter les entrées numériques via C0007 ou C0410 l Activer les entrées numériques de sorte que le variateur puisse se mettre en marche après le déblocage du variateur via la borne 3 Entrer la consigne Réglage Lenze Valeur de consigne 0 10 V Réglage individuel l Selon la position de l interrupteur DIP au niveau du module de fonction Génére...

Page 67: ...ctif sur la borne X3 28 déblocage variateur via borne ƒ Veillez à ce que le blocage variateur puisse être défini par le biais de plusieurs sources Ces sources agissent comme des contacts connectés en série ƒ Si malgré le déblocage variateur via la borne X3 28 l entraînement ne démarre pas vérifier si le blocage variateur est activé via une autresource Autre origine possible touche du clavier de co...

Page 68: ...aße 3 D 32699 Extertal Germany Service Lenze Service GmbH Breslauer Straße 3 D 32699 Extertal Germany 49 5154 82 0 008000 2446877 24 h helpline Ê 49 5154 82 2800 Ê 49 5154 82 1112 lenze lenze com service lenze com ü www lenze com EDK82ZAFSC 010 w DE EN FR 6 1 TD29 10 9 8 7 6 5 4 3 2 1 ...