Codes
Monitoring codes
l
95
EDS82ZAFPC201 EN 4.0
10.3
Monitoring codes
C0126: Behaviour with communication error
Code
Subcode
Index
Possible settings
Data type
Lenze
Selection
C0126
24449
(0x5F81)
10
0
[1]
10 FIX32
0: All monitoring functions deactivated.
2: Monitoring of internal communication
active
Monitoring of internal communication between function module and controller.
If the monitoring function is activated, a communication abort initiates TRIP (CE5).
,
Documentation for the standard device
Please refer to this documentation for a complete description of the setting
options of this code.
C1513: Monitoring response time of PZD communication
Code
Subcode
Index
Possible settings
Data type
Lenze
Selection
C1513
23062
d
=
5A16
h
3000
0
[1 ms]
65535 FIX32
The value of the response monitoring time is provided by the master.
)
Note!
A change in the monitoring time becomes effective immediately.
Monitoring starts with the receipt of the first telegram.
The setting
C1513 = 0
deactivates the monitoring function.