Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Mains connection, DC supply
l
95
EDS700ACBA EN 5.1
6.3.2
Mains connection, DC supply
ƒ
Power supply modules, mains chokes or mains filters may be connected to the mains
via unshielded single cores or unshielded cables.
ƒ
Cables between mains filters/RFI filters and power supply modules:
– Install twisted and with sufficient distance to adjacent cables.
– If cables are routed together in a cable duct or if longer cable lengths are used, we
recommend the use of shielded cables, e.g. between two control cabinets.
ƒ
The integrated DC busbars (X101/102) do not require EMC measures.
ƒ
Installation of cables for DC supply:
– Up to a length of 300 mm, twisted unshielded cables can be used, e.g. between an
upper and a lower installation row.
– From a length of 300 mm onwards, we recommend the use of shielded cables, e.g.
between two control cabinets.
ƒ
The cable cross−section must be dimensioned for the assigned fusing (observe
national and regional regulations).
Summary of Contents for E70AC Series
Page 1: ...EDS700ACBA Usx Usx Hardware Manual i700 l E70AC Servo Inverter i700 Translation...
Page 2: ...0Fig 0Tab 0...
Page 75: ...Mechanical installation 5 l 75 EDS700ACBA EN 5 1...
Page 147: ...Accessories overview Terminals 11 l 147 EDS700ACBA EN 5 1 E70AZEVK001 i700ZM001 A...
Page 148: ...Accessories overview Terminals 11 l 148 EDS700ACBA EN 5 1 E70AZEVK002 i700ZM001 C...
Page 149: ...Accessories overview Terminals 11 l 149 EDS700ACBA EN 5 1 E70AZEVK003 i700ZM001 B...
Page 150: ...Accessories overview Terminals 11 l 150 EDS700ACBA EN 5 1 E70AZEVK004 i700ZM001 D...
Page 151: ...Accessories overview Terminals 11 l 151 EDS700ACBA EN 5 1 E70AZEVK005 i700ZP005 a...
Page 152: ...Accessories overview Terminals 11 l 152 EDS700ACBA EN 5 1 E70AZEVK006 i700ZP005 b...
Page 161: ......