14
Parameter reference
14.3
Parameters of the communication module for slot MXI2
134
Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 10.2 EN · 11/2018 · TD06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14887
C14892
Parameter | Name:
C14887 | Suppress emergency message in case of
Data type: BITFIELD_8
Index: 9688 = 0x25D8
This code serves to prevent the emergency messages from being transmitted to the EtherCAT master. Here, errors
of a certain type can be suppressed deliberately. Furthermore, all errors are entered in the logbook.
A change will only be effective if no error number with the error type selected here is available in the standard device
code
C00165
.
Value is bit-coded:
Info
Bit 0 Fault
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning Locked
Bit 4 Warning
Bit 5 Information
Bit 6 Reserved
Bit 7 Reserved
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C14892 | Process data mode
Data type: UNSIGNED_8
Index: 9683 = 0x25D3
Mode selection for a time optimisation of the process data transfer
This code is only evaluated if "Distributed clocks" are used.
Synchronisation with "Distributed clocks" (DC) (
Selection list
(Lenze setting printed in bold)
Info
0 Optimised mode
This mode leads to a reduction of the dead time by one
EtherCAT cycle.
Preconditions:
• The EtherCAT telegram generated by the master has
a low jitter and is sent within a window of 320
μ
s
after the Sync0 event and shortly before the next
Sync0 event.
• The EtherCAT cycle time must be 1 ms.
1 Deterministic mode
This mode is the standard mode. It does not support a
time optimisation of the process data transfer.
The actual values are copied to the EtherCAT interface
with the next Sync0 event.
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT