
Commissioning
Activation of CANopen
6
59
KHB 13.0003-EN 2.0
6
Commissioning
6.1
Activation of CANopen
The controllers are default set to CAN bus communication.
931m_100
In the CAN Bus field, three parameters must be set:
ƒ
Node ID
For an unambiguous identification in the network, a node address must be assigned to
each node. Each node address may onlybe assigned once inthe network.The nodeaddress
is used to address the device.
ƒ
Baud rate
This parameter determines the baud rate in kBaud or kbits/s that is used on the CAN bus.
Please observe that high baud rates require a low maximum cable length.
ƒ
Bus terminator
If the controller is the lastnode ina bus system, theterminating resistormust beactivated.
When the physical connection to the master has been established, programming can be
started.
Note!
The controllers can either be parameterised and controlled via the serial
interface using the »fluxx« software or via the CAN bus.
In case of a CAN bus parameterisation and operation, the »fluxx« software
may be maximally operated in the operating mode ”Online Level 1”. If a higher
operating mode is selected, the »fluxx« software will have the parameter
change rights. In this case, the operating status cannot be changed via the
CAN.